20 Digits Token IP54 3 Phase Energy Meter Three Phase Energy Meter
20 Digits Token Three Phase Energy Meters , Low Credit Warning Tamper Protection
The CA368 is a three phase four-wire, compact design keypad based and STS token operated prepayment meter. It is in a compact BS housing and extrended transparent terminal cover. The meter is manufactured by ISO9001 standard with IP54 protection rating. Thanks to a wide range of power supply ( Un -40% +20%) and improved RF immunity withstand of 30V/m, it can operates in harsh environments.
The CA368 is ideal when separating accommodation; i.e. flats, apartments, houses offices where you have only one power supply. It is usually very expensive to pay a utility company to add extra supplies. Tiger Meters offer a low cost alternative and it allows you to keep control of your electricity usage.
Main Features
• 20 digits Token code topup
• Up to 13kV/6.5kA surge protection for lightening and other line surges
• IR optical & RS485 port allowing for easy data interrogation
• Shut off when credit finishes
• Programmable power limit and low credit warning
• Tamper detection and event record such as opening cover, reverse connection, black-out
• Dual power source working on both prepayment and credit mode
• Maximum demand measurement and load profiling (on request)
User Benefit
• Easy to install for both new reticulation and retrofitting due to BS mounting
• Low operational and inventory cost
• Can be ordered with PLC/ RF/ GPRS/GSM communication for AMR/AM I features
• Meter provides various valuable information by punching in Calin's short codes
• instant investment back, debt collection
Specifications:
Electrical parameters: | Electro Magnetic Compatibility |
| |
Nominal voltage Un | 3x240 voltage | Electrostatic discharges |
|
Limited voltage | 60%~120%Un | Contact discharge | 8kV |
Frequency | 50/60Hz+5% | Air discharge | 16kV |
Basic current(Ib) | 10A | Electromagnetic RF fields |
|
Maximum current(Imax) | 100A | 27MHz to 500MHz typical | 10V/m |
Starting current(Ist) | 30mA | 100kHz to 1GHz typical | 30V/m |
Active energy constant | 400imp/kWh | Fast transient burst test | 4kV |
Accuracy |
| Mechanical requirements |
|
Active energy to IEC62053‐21 | Class1.0 | Protection Rating | IP54 |
Reactive energy to IEC62053‐23 | Class2.0 | Insulation Classification | Protective Class II |
Power Consumption |
| Maximum cable size | 10 mm |
Power consumption in Voltage circuit | <2W <8VA |
|
|
Power consumption in current circuit | <1VA |
| |
Temperature range |
|
| |
Operation meter | 25 to+70℃ |
| |
Storage | 40 to+85℃ |
| |
|
| ||
Insulation strength |
| ||
AC Insulation strength | 4kV at 50Hz during 1min |
| |
Impulse voltage 1.2/50μs mains connections | 8kV |
|