HYPCIT series primary current injection tester is applied in power system for circuit breaker test, protection system test and | |||||||
current transformer test. The current injection tester generates a high current from power supply to simulate the rated current or | |||||||
fault current in the primary circuit of power equipment. The 1000A/15KVA HYPCIT primary injection test set is designed in | |||||||
integrated model. | |||||||
Product functions: | |||||||
1 High current output injected to the main circuit of power line to simulate the fault current. | |||||||
And then check whether the protection system will be operated according to the design | |||||||
2 High current output injected to the primary of current transformer and then measure the inducted current from secondary | |||||||
by error measurement instrument to check the ratio error and phase displacement of CT | |||||||
3 High current output injected to the main circuit of circuit breaker to simulate the rated current in primary. | |||||||
And then check the stability of circuit breaker according to the temperature rise procedure. | |||||||
4 Considered as a AC high current source in power equipment or cable test |
1 | Power supply: AC220V or AC 400V, 45Hz~65Hz. The power supply voltage is depends on the power output capacity, as below. | ||||||
2 | Typical output current: 500A or 1000A or 2000A | ||||||
Typical output capacity 3KVA or 5KVA or10KVA or15KVA | |||||||
It can be customized according to your requirements from above specs | |||||||
3 | Impendence voltage: 8% | ||||||
4 | Idle current: 6% | ||||||
5 | Current distortion <5% | ||||||
6 | Current is measured from the secondary of current transformer | ||||||
which is installed in the internal of the current booster. The display unit is 4 and 1/2 digitals current meter. | |||||||
Maximum measurement error 0.5%RDG+5D. | |||||||
7 | Timer indication of test running is an optional configuration. The timer could be customized according to the requirement of customer from the follow list: | ||||||
1) | 4 digital timer from 0~9999s / 0~999.9s /0~99.99s, accuracy 0.5%RDG+5D | ||||||
2) | 5 digital timer from 0~99999s / 0~9999.9s /0~999.99s, accuracy 0.2%RDG+2D | ||||||
3) | 6 digital timer from 0~999999s / 0~99999.9s /0~9999.99s, accuracy 0.1%RDG+1D | ||||||
8 | work temperature:0~40 C, Humidity <90% |