The performance of TP600-2U of inverter is at top of the market with peak efficiency up to 90% and small harmonics on DC side and it can be interfaced with RS232 and RS485.
- Dry Contact Outputs: The equipment must have dry contact outputs to report the basic alarms. You must have at least three dry contacts that report: No DC voltage at the input; No AC voltage at the input;
This is our popular one subrack inverter, we have more than 5000units sales every year.
Here are the Features;
- 19”1U or 19”2U
- High Frequency standby design with
- Transfer time 5-8ms
- Working mode selectable (AC priority or DC priority)
- High Frequency design
- DC/AC isolation improving system security
- System parameters programmable
- Complete protection
- Thermal controlled fan
- RS232 or RS485 communication port and Dry point
- Voltage adjustable 230Vac (200-240) or 110Vac (100-120)
- Front panel connection version available
LED shows
LED/Button | Symbol | Qty | Color | Status |
Silence | Silence button | 1 | Press continually for 1sec to turn ON INAUDIBLE | |
Mode | AC mode | 1 | Green | It illuminates when the mode is on AC mode |
Bypass | AC Bypass | 1 | Green | It illuminates when unit is on bypass mode |
Inverter | Inverter on | 1 | Green | It illuminates when inverter is normal operation |
Fault | Fault | 1 | Red | It is on in case of INVERTER faulty |
Battery capacity | 4 | Green | ≤25%,≤50%,≤75%,≤100% | |
Load level | Load | 4 | Green | ≤25%,≤50%,≤75%,≤100% |
DC low | 1 | Yellow | It illuminates when DC voltage is lower than limit | |
Overload | 1 | Yellow | It illuminates when load > 100% |
Structure
1.2.1 Do not expose to dust, rain, snow or liquids of any type,it is designed for indoor use. Do not block off ventilation, otherwise the INVERTER would be overheating.
1.2.2 To avoid fire and electric shock, make sure all cables selected with right gauge and being connected well. Smaller diameter and broken cable are not allowed to use.
1.2.3 Please do not put any inflammable goods near to inverter.
Specifications
TP600D and TP600E (110VDC/220VDC models)
Model | TP610 / TP620 / TP630 | TP640 / TP650 / TP660* |
Electrical | ||
DC Input | 110Vdc/ 125Vdc/220Vdc | |
DC Input | 110V/220V:-17%~+25%,125V:-20% ~+15% | |
AC input | 230Vac or 110Vac (-25%~+20%) | 230Vac (-25%~+20%) |
Frequency range | ±10% | |
Contious Power (40℃) | 1Kva - 6Kva | |
Power factor | 0.8 | 0.7 |
Nominal output voltage | 230Vac or 110Vac | 230Vac |
Voltage variation | Max ± 2% | |
Output frequency | 50/60Hz ± 0.1Hz | |
Efficiency | Max 90% | |
THD | <3% liner load | |
<5% non-liner load | ||
Crest factor | .3:1 | |
Overload | 125% 60secs (TP660 10secs) | |
110% 10mins (TP660 30secs) | ||
Transfer time | 5-8ms | |
Dynamic response time | < 30ms | |
LVD | 91.5,104Vdc or 183Vdc | |
Display & Communication | ||
Communication Interface | RS232 and RS485 | |
4xDry contact | ||
Safety & Environment | ||
Operating Temp. | Full load, <-20℃> - 40℃ | |
Derating using, 40℃ - 60℃ | ||
Isolation | 2000Vrms | |
Mechanical | ||
Dimension (WxH) | 19"2U | |
Depth | 256mm / 321mm | 321mm |
Weight | 6kgs / 12kgs | 12kgs |
Cooling | forced fan with thermal control | |
Enclosure | IP20 | |
Standard | ||
LVD | EN60950-1 | |
EMC | EN55022 |