Combined with modern semiconductors and sophisticated control algorithm, TP600 series
inverter could achieve a compact size of maximized power density.
To protect battery, TP600 can only be powered on while battery voltage fall into DC operated range. When battery voltage feel to the level of warning point, audible alarm will be started and it will continue output until the voltage fall under the low voltage disconnect point. When the units are shut down due to DC low, only when the DC voltage is back to the normal value, the units will start up automatically.
Features:
- 19”1U or 19”2U
- High Frequency standby design with
- Transfer time 5-8ms
- Working mode selectable (AC priority or DC priority)
- High Frequency design
- DC/AC isolation improving system security
- System parameters programmable
- Complete protection
- Thermal controlled fan
- RS232 or RS485 communication port and Dry point
- Voltage adjustable 230Vac (200-240) or 110Vac (100-120)
- Front panel connection version available
Specifications
TP600D (110VDC /125VDC models)
Model | TP610 / TP620 / TP630 | TP640 / TP650 / TP660* |
Electrical | ||
DC Input | 110Vdc/ 125Vdc/ | |
DC Input | 110V/220V:-17%~+25%,125V:-20% ~+15% | |
AC input | 230Vac or 110Vac (-25%~+20%) | 230Vac (-25%~+20%) |
Frequency range | ±10% | |
Contious Power (40℃) | 1Kva - 6Kva | |
Power factor | 0.8 | 0.7 |
Nominal output voltage | 230Vac or 110Vac | 230Vac |
Voltage variation | Max ± 2% | |
Output frequency | 50/60Hz ± 0.1Hz | |
Efficiency | Max 90% | |
THD | <3% liner load | |
<5% non-liner load | ||
Crest factor | .3:1 | |
Overload | 125% 60secs (TP660 10secs) | |
110% 10mins (TP660 30secs) | ||
Transfer time | 5-8ms | |
Dynamic response time | < 30ms | |
LVD | 91.5,104Vdc | |
Display & Communication | ||
Communication Interface | RS232 and RS485 | |
4xDry contact | ||
Safety & Environment | ||
Operating Temp. | Full load, <-20℃> - 40℃ | |
Derating using, 40℃ - 60℃ | ||
Isolation | 2000Vrms | |
Mechanical | ||
Dimension (WxH) | 19"2U | |
Depth | 256mm / 321mm | 321mm |
Weight | 6kgs / 12kgs | 12kgs |
Cooling | forced fan with thermal control | |
Enclosure | IP20 | |
Standard | ||
LVD | EN60950-1 | |