TBB TP600 series inverter could achieve a compact size of maximized power density. Here are the Features;
Standalone design
LED Shows
Input voltage | 24V | 48V | 110V | 125V | 220V | 240V |
Power on voltage(VDC) | 21~29 | 42~58 | 98~138 | 105~139 | 195~276 | 210~292 |
DC voltage operated range(VDC) | 20~30 | 40~60 | 93~143 | 100-144 | 186~286 | 198~302 |
Low voltage warning (VDC) | 22 | 44 | 101 | 105 | 202 | 218 |
Notes:
1. To protect battery, HTM250 can only be powered ON while battery voltage fall into DC operated range.
2. When battery voltage fell to the level of warning point, audible alarm will be started and it will continue output until the voltage fall under the low voltage disconnect point.
Specifications
TP600M and TP600S (24VDC/48VDC models)
Model | TP610 / TP620 / TP630 | TP640 / TP650 / TP660 |
Electrical | ||
DC input | 24Vdc or 48Vdc | 48Vdc |
Dc input range | .-17% ~ +25% | |
AC Input | ||
AC input | 230Vac or 110Vac (-25%~+20%) | 230Vac (-25%~+20%) |
Frequency range | ±10% | |
Output power | 1kva, 2kva, 3kva | 4kva, 5kva, 6kva |
Wave form | Pure sine wave | |
Power factor | 0.8 * | 0.7 |
Nominal output voltage | 230Vac or 110Vac | 230Vac |
Voltage variation | Max ± 2% | |
Output frequency | 50/60Hz ± 0.1Hz | |
Efficiency | Max 88% | |
THD | <3% liner load | |
<5% non-liner load | ||
Crest factor | .3:1 | |
Overload | 125% 10secs | |
110% 10mins | ||
Transfer time | 5-8ms | |
Dynamic response time | < 30ms | |
LVD | 20Vdc or 40Vdc | 40Vdc |
Display & Communication | ||
Communication Interface | RS232 and RS485 | |
4xDry contact | ||
Safety & Environment | ||
Operating Temp. | Full load, <-20℃> - 40℃ | |
Derating using, 40℃ - 60℃ | ||
Isolation | 1500Vrms | |
Mechanical | ||
Dimension (WxH) | 19"2U | |
Depth | 256mm / 321mm / 390mm | 321mm / 390mm |
Weight | 6kgs / 12kgs /15kgs | 12kgs / 15kgs |
Cooling | forced fan with thermal control | |
Enclosure | IP20 | |
Standard | ||
LVD | EN60950-1 | |
EMC | EN55022 |