TP600-1U Series
Standalone Pure Sine Wave Inverter - Telecom market
Combined with modern semiconductors and sophisticated control algorithm, TP600 series
inverter could achieve a compact size of maximized power density.
TP600 series standalone inverter was a standby design with an integrated utility bypass. With
a dip switch, the inverter can be set into either AC priority mode or DC priority mode.
- Rated power: greater than or equal to 2,5KVA.
- Architecture: "Stand alone" rackable in 19 ".
- automatic bypass: the equipment have 48VDC and 220VAC inputs so that in the event of an operational input failure, the equipment transfers load to the alternate input automatically, and the interruption or disturbance in the output must last less than or equal to 10ms. The team
have the ability to choose from which input the load will be fed. In the case where the load is fed through the AC input, the equipment have a filter against electromagnetic interference in order to improve the output waveform.
- Control by keyboard and front screen, should include:
• Real-time measurements of input and output values (voltages,
currents and frequencies).
• Alarms.
• Choice of input source (DC or AC).
Features
- 19”1U or 19”2U
- High Frequency standby design with
- Transfer time 5-8ms
- Working mode selectable (AC priority or DC priority)
- High Frequency design
- DC/AC isolation improving system security
- System parameters programmable
- Complete protection
- Thermal controlled fan
- RS232 or RS485 communication port and Dry point
- Voltage adjustable 230Vac (200-240) or 110Vac (100-120)
- Front panel connection version available
Specification
TP600M and TP600S (24VDC/48VDC models)
Model | TP605 | TP610 |
Electrical | ||
DC input | 24Vdc or 48Vdc | 48Vdc |
Dc input range | .-17% ~ +25% | |
AC Input | ||
AC input | 230Vac or 110Vac (-25%~+20%) | 230Vac (-25%~+20%) |
Frequency range | ±10% | |
Output power | 500va | 1kva |
Wave form | Pure sine wave | |
Power factor | 0.8 * | 0.8 |
Nominal output voltage | 230Vac or 110Vac | 230Vac |
Voltage variation | Max ± 2% | |
Output frequency | 50/60Hz ± 0.1Hz | |
Efficiency | Max 88% | |
THD | <3% liner load | |
<5% non-liner load | ||
Crest factor | .3:1 | |
Overload | 125% 10secs | |
110% 10mins | ||
Transfer time | 5-8ms | |
Dynamic response time | < 30ms | |
LVD | 20Vdc or 40Vdc | 40Vdc |
Display & Communication | ||
Communication Interface | RS232 and RS485 | |
4xDry contact | ||
Safety & Environment | ||
Operating Temp. | Full load, <-20℃> - 40℃ | |
Derating using, 40℃ - 60℃ | ||
Isolation | 1500Vrms | |
Mechanical | ||
Dimension (WxH) | 19"1U | |
Depth | 319mm | 319mm |
Weight | 4kgs | 4.5kgs |
Cooling | forced fan with thermal control | |
Enclosure | IP20 | |
Standard | ||
LVD | EN60950-1 | |
EMC | EN55022 |