CSA listed smart modulating electric actuator/complied to UL standard
Features
Description
DCL modulating type electric actuator is controlled by a smart compact controller that can choose two type input signals for different applications. Commonly, 4-20mA and 2-10V optional, special, 4-20mA and 1-5V optional.In some industry fields those exists two types of input signals, or faces system upgrades, DCL smart modulating type electric actuator can be replacement without changing control pack.
Actuator has been rigorous tested by CSA per UL and CSA standard. The duty rate can be over 70% for all series. The EPS system is self-calibrating which virtually eliminates "hunting" and provides an output position monitoring signal as standard.
Specification
Type | DCL-05E | DCL-10E | DCL-20E | DCL-40E | DCL-60E | DCL-100E | DCL-160E | DCL-250E |
Power | AC24/110/220 | AC24/110/220 | AC24/110/220 | AC24/110/220 | AC24/110/220 | AC110/220 | AC110/220 | AC110/220 |
Output Torque | 50Nm | 100Nm | 200Nm | 400Nm | 600Nm | 1000Nm | 1600Nm | 2500Nm |
Acting Time | 20S | 30S | 30S | 30S | 45S | 30S | 48S | 75S |
Turning Angle | 0-90° | 0-90° | 0-90° | 0-90° | 0-90° | 0-90° | 0-90° | 0-90° |
Motor Power | 10W | 25W | 40W | 90W | 90W | 120W | 140W | 140W |
Rated Current | 1.50/0.24/ 0.16A | 2.12/0.57/ 0.35A | 3.65/0.65/ 0.37A | 6.80/1.12/ 0.57A | 6.80/1.18/ 0.60A | 1.93/0.94A | 1.75/0.96A | 1.75/0.98A |
Total Weight | 2.5kg | 4.5kg | 9kg | 9.5kg | 10kg | 19kg | 19.5kg | 20kg |
Input Signal | 4-20mADC,1-5VDC,2-10VDC | |||||||
Output Singal | 4-20mADC | |||||||
Basic Error | not more than ±1% | |||||||
Reciprocating Error | not more than 1% | |||||||
Dead Space | 0.5%-5.0% adjustable | |||||||
Damping Characteristic | 0 times | |||||||
Repeating Error in Actuator | ≤1% | |||||||
Insulating Resistance | AC24V:100MΩ/250VDC AC110/220V:100MΩ/500VDC | |||||||
Withstand Voltage Class | AC24V:500VAC 1minute AC110/220V:1500VAC 1minute | |||||||
Protection Class | IP67 | |||||||
Installation Angle | 360°at any angle | |||||||
Electric Interface | Two G1/2 Wate-proof Cable Connectors,one for power line and one for signal line | |||||||
Ambient Temperature | -20℃~+55℃ | |||||||
Optional Function | Over-torque protector/Dehumidify Heater/Passive contact switch/Dome indicator/Handle | |||||||
Remark | Any other input or output signal needed, please specified in purchase order. |