MODEL | ZGD-1K (L) | ZGD-2K (L) | ZGD-3K (L) | |
PHASE | Single phase with ground | |||
CAPACITY | 1000 VA / 800 W | 2000 VA / 1600 W | 3000 VA / 2400 W | |
INPUT | ||||
Nominal Voltage | 100/110/115/120/127VAC or 200/208/220/230/240VAC | |||
Input Voltage Range | 55-145 VAC or 110-300 VAC | |||
Frequency Range | 40Hz ~ 70 Hz | |||
Power Factor | ≥ 0.99 @ Nominal Voltage (100% load) | |||
OUTPUT | ||||
Output Voltage | 100/110/115/120/127VAC or 200/208/220/230/240VAC | |||
Voltage Regulation | ± 1% | |||
Frequency Range (Synchronized Range) | 47~ 53 Hz or 57 ~ 63 Hz | |||
Frequency Range (Batt. Mode) | 50 Hz or 60Hz ± 0.1 Hz | |||
Current Crest Ratio | 3:1 | |||
Harmonic Distortion | ≤ 3 % THD (Linear Load) ≤ 6 % THD (Non-linear Load) | |||
Transfer Time | AC to DC | Zero | ||
Inverter to Bypass | 4 ms (Typical) | |||
Waveform (Batt. Mode) | Pure Sinewave | |||
EFFICIENCY | ||||
To AC Mode | 88% | 89% | 90% | |
To Battery Mode | 83% | 87% | 88% | |
BATTERY | ||||
Standard model machine | Battery type | 12V9AH | ||
Quantity | 2 | 4 | 6 | |
Standard charging time | 4 hours charge to 90% | |||
max charge current | 1A | |||
Charging voltage | 27.3VDC±1% | 82.1VDC±1% | ||
Long-run Model | Battery Type | Depending on the capacity of external batteries | ||
Numbers | 2 or 3 | 4 or 6 or 8 | 6 or 8 | |
Charging Current (max.) | 1.0A/2.0A/4.0A/6.0 A | |||
Charging Voltage | 41.0VDC ± 1% | 82.1 VDC ±1% | 109.4VDC ±1% | |
INDICATORS | ||||
LCD | Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators | |||
ALARM | ||||
Battery Mode | Sounding every 4 seconds | |||
Low Battery | Sounding every second | |||
Overload | Sounding twice every second | |||
Fault | Continously sounding | |||
PHYSICAL | ||||
Standard models | Dimension | 282*145*220 | 397*145*220 | 419*190*318 |
Net weiZGDt(kgs) | 9.3 | 18.6 | 30 | |
Long-run Model | Dimension | 282*145*220 | 397*145*220 | |
Net WeiZGDt (kgs) | 4.6 | 6.8 | 7.4 | |
ENVIRONMENT | ||||
Humidity | 20-90 % RH @ 0- 40°C (non-condensing) | |||
Noise Level | Less than 50dBA @ 1 Meter | |||
MANAGEMENT | ||||
Smart RS-232/USB | Supports Windows 2000/2003/XP/Vista/2008/7/8, Linux, Unix, and MAC | |||
Optional SNMP | Power management from SNMP manager and web browser | |||
*Long-run model is only available in 200/208/220/230/240VAC systems. | ||||
**Derate to 80% of capacity in Frequency converter mode and to 80% when the output voltage is adjusted to 100/200/208VAC | ||||
* Product specifications are subject to change without further notice |