The outdoor UPS system has good protection function: such as heat insulation,dustproof, damp proof, waterproof etc.
● The advanced PFC technology, improves the input power factor close to utility, raises the power efficiency, removes the harmonic noise from UPS to utility, lowers UPS operational cost, it’s really a good environmental protection power supply.
● Smart management function. If main power blackout, ups will transfer to backup mode to supply loads. When battery voltage is low, ups would protect itself and shuts down. When the main power recovers, the UPS would check the main power itself, if the main power is also normal, ups would turn on automatically to supply loads; if main power is abnormal, UPS would just turn on charger to charge the battery until the main power is normal.
● Advanced voltage compensation technique, makes the input voltage range from 115VAC to 295VAC, using batteries less, enhancing the adaptability against the bad power condition.
● Advanced wide input frequency technique, makes the input frequency range from 45Hz to 55Hz, compatible with generator under variable circumstance.
● DC start function, when there is no main power; UPS can be turned on by battery, to meet the user’s emergency needs. The cold start function is quite strong. UPS can be cold started on full load situation.
Model | 1KVA | 2KVA | 3KVA | 6KVA | 10KVA |
Range voltage | 220/230/240VAC | ||||
Frequency | 50Hz/62Hz | ||||
Input | |||||
Voltage range | 115~295VAC(±3VAC) | 176~297VAC(±3VAC) | |||
Frequency Range | 50Hz (46~54 Hz) ; 60Hz (56~64 Hz) | ||||
Soft Start | 0~100% 5sec | ||||
Power factor | 0.98 | ||||
Output | |||||
Voltage Precision | 220/230/240VAC(1±2%)AC | ||||
Frequency Precision | 50Hz/62Hz±0.05Hz | ||||
Power factor | 0.7/0.8(optional) standard 0.7 | ||||
Wave Distortion | Linear load<3% Non-linear load<6% | ||||
Overload capability | Overload(110~150%)for 30 seconds,then automatically transfer to bypass.When load is normal,it can automatically transfer to normal mode | ||||
Crest Factor | 3:01 | ||||
Transfer time | 0ms (AC to DC) | ||||
battery | 36VDC | 72VDC | 96VDC | 240VDC | 240VDC |
Charging current | 4A/8A(optional) | 4A/8A(optional) | 4A/8A(optional) | 4.2A | 4.2A |
Internal Battery Caoacity | (38/65/80/100AH) optional | ||||
Panel display | |||||
LED | Load level/Battery level ,Battery indicator,Utility power,Inverter ,Bypass,Overload ,Fault | ||||
Communications | |||||
Communications interface | RS232 SNMP card(optional) | ||||
Work Environment | |||||
Temperature | -40~55ºC | ||||
Humidity | 0~95%(Non-condensing | ||||
Storage Temperature | -25ºC~55ºC | ||||
Elevation | <1500m | ||||
Physical Characteristics | |||||
Weight(KG)N.W | 85 | 125 | 125 | 150 | 150 |
Dimensions:(WxDxH)mm | 613*640*954 | 650*753*1227 | 650*753*1227 | 940*940*1770 | 940*940*17 |