The ZGD330 is supplied with Watch & Save 3000 software as standard and can be remotely monitored using the Power Net Guard system from anywhere in the world. Additional battery extension packs allow the standard battery routine to be extended up to several hours.
Application:
Servers,
Local area Network(LAN),
Data centers,
Telecommunications,
Electro-medical equipment
Model power | ZGD330 10-200KVA | |||||||||||
10KVA | 15KVA | 20KVA | 30KVA | 40KVA | 60KVA | 80KVA | 100KVA | 120KVA | 160KVA | 200KVA | ||
Capacity | 8KW | 12 KW | 16 KW | 24 KW | 32 KW | 48 KW | 64 KW | 80 KW | 96KW | 128 KW | 160 KW | |
Input | ||||||||||||
Rated voltage | 380/400/415 Vac three-phase | |||||||||||
Voltage range | ±20% | |||||||||||
Frequency range | 45-65Hz | |||||||||||
Power factor | >0.92with harmonic filter | |||||||||||
Current harmonic distortion | <5%with harmonic filter | |||||||||||
Soft Start | 0-100% in10" | |||||||||||
Bypass Input | ||||||||||||
Rated voltage | 380/400/415 Vac three-phase | |||||||||||
Permitted voltage range | ±15%(selectable from ±10% to ±25% from front panel) | |||||||||||
Rated frequency | 50/60Hz | |||||||||||
Permitted frequency range | ±2%(selectable from ±1% to ±5% from front panel) | |||||||||||
Standard features | Back Feed protection; split bypass line | |||||||||||
Batteries | ||||||||||||
Type | Maintenance-free lead-acid VRLA AGM / GEL;NICd | |||||||||||
Battery voltage | 384VDC | 480VDC | ||||||||||
Maximum recharge current(A) | 0.2×C10 | |||||||||||
AC ripple voltage | <1% | |||||||||||
Inverter Output | ||||||||||||
Number of phases | 3+N | |||||||||||
Rated voltage(V) | 380Vac | |||||||||||
Regulation of the output voltage | 380~424Vac phase/neutral(from control panel) | |||||||||||
Crest factor (Ipeak / Irms) | 3:1 | |||||||||||
Static stability | ±1% | |||||||||||
Dynamic stability | ±5% | |||||||||||
Frequency | 50/60Hz configurable | |||||||||||
Overload | 110% 125% 150% of the rated current for 5h/10'/1' | |||||||||||
Frequency stability | ±0.05% on mains failure;±2%(selectable from ±1% to ±5%)with mains supply present | |||||||||||
Remote signaling | Volt free contacts | |||||||||||
Remote controls | EPO and Bypass | |||||||||||
Communication | RS232 + romote contacts | |||||||||||
Operation temperature | 0ºC/ + 40ºC | |||||||||||
Relative humidity | <95% non condensing | |||||||||||
Noise | 54dBA at 1m | 50-65dBA at 1m | ||||||||||
Protection degree | IP20 | |||||||||||
Efficiency smart mode | up to 98% | |||||||||||
Compliance | Safety:EN 62040-1-1(Directive 2006/95/EC); EMC:6200-2(Directive 2004/108/EC) |
High intelligence and reliable power supply:
ZGD330 provides maximum protection for vital mission-critical networks, security applications (electro- medical)and industrial applications thanks to its outstanding mechanical and electrical design.
The load is powered continuously by the inverter with a filtered, stabilized and regulated sine wave supply. The input and output EMI filters considerably increase the immunity of the load to mains disturbances and surges.
The ZGD330 uses on-line double conversion technology (VFI) with isolation transformer on the inverter output.