2KVA 110V 120V High Frequency Online UPS Double Conversion
High Frequency Igbt Ups 2KVA 110V 120V Online Double Conversion Computer Ups
S Series single phase Uninterruptible Power Supply (UPS) is a new generation product incorporating advance digital control technology and double-conversion power topology, the product capable of working with ultra wide range of electric input with high efficiency and reliability, protect mission critical equipment with clean, safe, high-quality AC power supply. The S Series UPS user friendly interface make it easy to use, the small dimension for saving valuable installation space, perfectly meet infrastructure needs in areas of IT, finance, traffic control, manufacturing industry, education and government etc
Model item | 1K(R) | 1K(R)S | 2K(R) | 2K(R)S | 3K(R) | 3K(R)S | 6K | 6K(R)S | 10K | 10K(R)S | |
Rated power | 1000VA/800W | 2000VA/1600W | 3000VA/2400W | 6kVA/5.4kW | 10kVA/9kW | ||||||
AC Input | Input system | Single phase (L/N+PE) | |||||||||
| Nominal voltage | HV: 208/220/230/240Vac LV:100/110/120/127Vac | |||||||||
| Frequency | 50/60Hz | |||||||||
| Voltage range | HV: 90~300VAC±5VAC LV: 60-145Vac±3VAC | |||||||||
| Frequency range | (40~70)±0.5Hz | |||||||||
| Input power factor | >0.99 | |||||||||
| Bypass Voltage Range | HV: 115~285VAC×(1±3%) LV: 80~140VAC×(1±3%) | |||||||||
Battery Input | Nominal Voltage | 24V | 36V | 48V | 72V | 72V | 96V | 192V | 192V | 192V/240V | |
| Battery Capacity & Quantity | 12V/9AH x 2pcs | External | 12V/9AH x 4pcs | External | 12V/9AH x 6pcs | External | 12V/9AH x 16pcs | External | 12V/9AH x16/20pcs | External |
| Backup Time | Half loaded≥8minutes, Full loaded ≥3minutes(standard) | Half loaded≥6minutes, Full loaded ≥3minutes(standard) | ||||||||
| Battery charger time | Charger to 90% battery capacity in 5 hours(standard) Dependent on the capacity of external batteries (long backup time) | |||||||||
AC Output | Output system | Single phase (L/N+PE) | |||||||||
| Inverter Mode Output voltage | HV:208/220/230/240Vac±2% LV:100/110/120/127Vac±2% | |||||||||
| Waveform | Sine Wave THD<3% (linear load) THD<7% (nonlinear load) | Sine Wave THD<2% (linear load) THD<5% (nonlinear load) | ||||||||
| Output frequency | 50/60±4Hz (Sync mode) 50/60Hz±1% (Fix Freq. mode) |