Specifications
Brand Name :
HAROK
Model Number :
VF008 DC
MOQ :
3000
Standard :
IEC/EN 60947-2, RoHS
Rated voltage :
up to 1000V
Rated current :
up to 63A
Ambient temperature :
-35℃ - + 70℃(Refer to 4.3)
atmosphere condition :
≤95%
Pollution degree :
ll
Altitude :
≤2000m(if exceed 2000m, Refer to 4.4)
Rate Current In :
1A,2A,3A,4A,6A,10A,13A,16A,20A,25A,32A.40A,50A,63A
Description

VF008 DC Circuit BreakerVF008 PV System Protection DC Circuit Breaker IEC/EN 60947-2 Standard

1. General

1.1 Standard: IEC/EN 60947-2 ,RoHS;

1.2 Rated voltage up to 1000V, Rated current up to 63A;

1.3 Protection of circuits against overload currents;

1.4 Protection of circuits against short- circuit currents;

1.5 VF008 DC circuit-breakers are used in communication systems and PV DC systems.

2. Features

2.1 Excellent breaking capacity

2.2 Double connection function of lead wire and bus bar

2.3 Stored energy operation, fast closing, long service life

2.4 Convenient installation, disassembly

2.5 Contact on-off indication, higher security

2.6 Green environmental protection and energy saving

3. Operating conditions

3.1 Ambient temperature: -35℃ - + 70℃(Refer to 4.3)

3.2 The atmosphere condition: ≤95%

3.3 Pollution degree: ll

3.4 Altitude: ≤2000m(if exceed 2000m,Refer to 4.4)

4. Technical data

4.1 Classification

4.1.1 Rate Current In:

1A,2A,3A,4A,6A,10A,13A,16A,20A,25A,32A.40A,50A,63A

4.1.2 Number of poles: 1P, 2P, 4P

4.1.3 Tripping curves: C Type, (7-10)In

4.2 Parameters

4.2.1 Rated breaking capacity Icu

Rated current In (A) Number of poles Rated voltage Ue (V) Rated breaking capacity Icu (A)
1-63 1 250 6000
2 500 6000
4 1000 6000

4.2.2 Electrical and mechanical life

a. Electrical life: >1500

b. Mechanical life: >20,000

4.2.3 Rated impulse withstand voltage Uimp: 4KV

4.2.4 (28-32)℃ ambient temperature over-current protection features.

Test Test current

Initial

state

Time limit for tripping or not tripping

Expected

result

Remark
a 1.05In Cold state t≤1h Not tripping
b 1.30In Right after test number a t<1h Tripping The current is rising within 5s
c 7In Cold state t≤0.2s Not tripping
d 10In Cold state t<0.1s Tripping

Note: The terminology”Cold state”means that the test is performed at the base calibration temperature with no load prior to the test.

4.3 Temperature derating

Rated current (A) Temperature compensation coefficient under various operational temperature.
-35℃ -30℃

-20℃

-10℃

0℃

10℃

20℃

30℃

40℃

50℃

60℃

70℃

1 1.3 1.26 1.23 1.19 1.15 1.11 1.05 1 0.96 0.93 0.88 0.83
2 2.6 2.52 2.46 2.38 2.28 2.2 2.08 2 1.92 1.86 1.76 1.66
3 3.9 3.78 3.69 3.57 3.42 3.3 3.12 3 2.88 2.79 2.64 2.49
4 5.2 5.04 4.92 4.76 4.56 4.4 4.16 4 3.84 3.76 3.52 3.32
6 7.8 7.56 7.38 7.14 6.84 6.6 6.24 6 5.76 5.64 5.28 4.98
10 13.2 12.7 12.5 12 11.5 11.1 10.6 10 9.6 9.3 8.9 8.4
13 17.16 16.51 16.25 15.6 14.95 14.43 13.78 13 12.48 12.09 11.57 10.92
16 21.12 20.48 20 19.2 18.4 17.76 16.96 16 15.36 14.88 14.24 13.44
20 26.4 25.6 25 24 23 22.2 21.2 20 19.2 18.6 17.8 16.8
25 33 32 31.25 30 28.75 27.75 26.5 25 24 23.25 22.25 21
32 42.56 41.28 40 38.72 37.12 35.52 33.93 32 30.72 29.76 28.16 26.88
40 53.2 51.2 50 48 46.4 44.8 42.4 40 38.4 37.2 35.6 33.6
50 67 65.5 63 60.5 58 56 53 50 48 46.5 44 41.5
63 83.79 81.9 80.01 76.86 73.71 70.56 66.78 63 60.48 58.9 55.44 52.29

4.4 Altitude derating

Tripping type Rated current In (A) Current correction factor For example
≤2000 2000~3000m ≥3000m
C

1, 2, 3, 4, 6, 10,

13, 16, 20, 32, 40, 50, 63

1 0.9 0.8

Rated current of 10A products rated

current derating 2500m: 0.9×10=9A

4.5 Curves shown in Figure 1

VF008 PV System Protection DC Circuit Breaker IEC/EN 60947-2 Standard

4.6 Wiring: Apply to 25 mm wire connection terminals

Tightening torque 2.5N·m

Rated current In (A)

Copper wire nominal

cross sectional area(mm²)

1~6 1
10 1.5
13, 16, 20 2.5
25 4
32 6
40, 50 10
63 16

4.7 Each pole power consumption of the circuit breaker

Rated current In (A)

Copper wire nominal

cross sectional area(mm²)

1~6 1
10 1.5
13, 16, 20 2.5

4.8 DC application wiring diagram shown in Figure 2

VF008 PV System Protection DC Circuit Breaker IEC/EN 60947-2 Standard

Wiring diagram description:

1. 〇+Positive 〇-Negative

2. L+ Load positive L- Load negative

3. Prohibit power reversed

4. Rated voltage: 1P: 250V, 2P: 500V, 4P: 1000V

5. Strictly forbidden to remove the four poles products of sealing plug wiring operation.

5. Overall and mounting dimensions (mm)

VF008 PV System Protection DC Circuit Breaker IEC/EN 60947-2 Standard

Send your message to this supplier
Send Now

VF008 PV System Protection DC Circuit Breaker IEC/EN 60947-2 Standard

Ask Latest Price
Brand Name :
HAROK
Model Number :
VF008 DC
MOQ :
3000
Standard :
IEC/EN 60947-2, RoHS
Rated voltage :
up to 1000V
Rated current :
up to 63A
Contact Supplier
VF008 PV System Protection DC Circuit Breaker IEC/EN 60947-2 Standard