Specifications
Brand Name :
HAROK
Model Number :
VRL02
Place of Origin :
CHINA
MOQ :
3000PCS
Payment Terms :
L/C, T/T
Poles number :
1P+N
Rated voltage :
AC240V
Mechanical life :
2000
Standard :
IEC/EN 61009-1
Rated frequency :
50/60Hz
Rated Current :
6A, 10A, 16A, 20A, 25A, 32A, 40A, ,45A, 50A
Electrical life :
2000
CURVE :
TYPE B
Description

VRL02 1P+N Mini RCBO Type B With Rated Current 6A, 10A, 16A, 20A, 25A, 32A, 40A, ,45A, 50Amini RCBO | Residual Current Operated Circuit Breaker with over-current protection

VRL02 Mini RCBO

(MCB sized 1 module with switched neutral)

1. General

1.1 Function

VRL02B RCBO type B and VRL02B+ RCBO type B+ are appearance design, compact structure, good reliability, and high safety. They are universal residual current circuit breaker with Overcurrent protection(RCBO).

Rated current up to 63A and for purposes of residual current protection, overcurrent (overload) and short circuit protection. When any personal electric shock occurs or the circuit leakage current exceeds the predetermined value, the RCBO can automatically cut off the power supply in a very short period of time, so that the safety of persons and electrical equipment can be operated.

Residual current circuit breaker with Overcurrent protection(RCBO) type B are suitable for domestic as well as industrial applications, where are used frequency inverters, PV plant, EV chargers and similar elements. B type provides a sensitivity to residual AC, pulsating and smooth DC current, together with high frequencies up to 1 kHz.

Residual current circuit breaker with Overcurrent protection(RCBO) type B+ meet full type B feature , with additional tripping values are defined up to 20KHZ and they are below 420mA.

They are based on electronic technology, which brings advantages of more accurate measuring of residual current and, as a consequence, reduction of unwanted tripping. These devices also do not suffer with magnetization of the tripping unit.

2. Technical parameters

2.1 The tripping characteristic curves are as shown below.

VRL02 1P+N Mini RCBO Type B With Rated Current 6A, 10A, 16A, 20A, 25A, 32A, 40A, ,45A, 50A

2.2 Basic parameters

Standard IEC/EN 61009-1, AS/NZS 61009.1
Main Specifications Model No. VRL02
Rated current In 6A, 10A, 16A, 20A, 25A, 32A, 40A, ,45A, 50A
Classified by Type of Instantaneous Tripping Type B: (3 ~ 5) In, Type C: (5 ~ 10) In
Poles 1P + N
Type (wave form of the earth leakage sensed) Type B
;Mechanical features Rated voltage Ue AC240V
Frame size rated current Inm 50A
Rated residual operating current I△n 0.01A, 0.03A, 0.1A, 0.3A
Rated residual non-operating current I△no 0.005A, 0.015A, 0.05A, 0.15A
Rated short-circuit breaking capacity Icn 230/240V 6000A, 10000A; 120V 15000A

Rated residual making and

breaking capacity I△m

500A
Electrical life 2,000
Mechanical life 2,000
Rated impulse withstand voltage Uimp 6000V
Connection From top and bottom, from bottom and top

2.3 The residual current breaking times

In (A) I△n (A) Breaking time when the residual current assumes the following values (s)
I△n 2I△n 5I△n 5A, 10A, 20A, 50A, 100A, 200A, 500A(a) I△t(b)
5~40 0.006, 0.01, 0.03, 0.1, 0.3 0.1 0.05 0.04 0.04 0.04

a. For tests of 5A, 10A, 20A, 50A, 100A, 200A and 500A, the current values beyond the lower limit of over-current instantaneous tripping are not tested.

B. Tests are done when I△t is equal to the lower limit current of over-current instantaneous tripping of type B and type C.

2.4 The over-current protection characteristics

No. Rated current In (A) Initial state Test current (A) Specified time (t) Expected result Remarks
a 6 ~ 40 Cold state 1.13 In t ≥ 1h Non-tripping
b Immediately after sequence a 1.45 In t < 1h Tripping Increase to the specified current within 5s after test item a.
c Cold state 2.55 In 1s < t < 60s Tripping
d Cold state 3 In t ≥ 0.1s Non-tripping Type B
5 In t < 0.1s Tripping
5 In t ≥ 0.1s Non-tripping Type C
10 In t < 0.1s Tripping

3. Outline and installation dimensions (mm)

VRL02 1P+N Mini RCBO Type B With Rated Current 6A, 10A, 16A, 20A, 25A, 32A, 40A, ,45A, 50A

Product Description:

RCBO Type B is a type of circuit breaker designed to protect people and property from electric shocks and fires. It is classified by type of instantaneous tripping as Type B (3~5 In) and Type C (5~10 In). This product has a remarkable electrical life of 2000 and is available in 1P+N poles configuration. RCBO Type B offers superior protection against overload, short-circuit, and earth leakage. It is an ideal choice for both commercial and industrial applications due to its efficient performance and reliable safety features. This product is designed to meet the highest safety standards and provides an essential layer of protection for people and property.

Features:

  • Product Name: RCBO Type B
  • Rated impulse withstand voltage Uimp: 6000V
  • Rated Residual Operating Current: 0.01A, 0.03A, 0.1A, 0.3A
  • Rated Residual Non-Operating Current: 0.005A, 0.015A, 0.05A, 0.15A
  • Rated residual making and breaking capacity I△m: 500A
  • Classified by Type of Instantaneous Tripping: Type B: (3 ~ 5) In, Type C: (5 ~ 10) In
  • Residual Current Operated Circuit Breaker (RCBO)

Applications:

HAROK VRL22 2P,4P VRL11 VAL003 VKL003 VDL006 VRL01 VRL02 VRL03 VK007LE 1P-4P is the RCBO Type B which has the rated residual non-operating current 0.005A, 0.015A, 0.05A, 0.15A, poles 1P+N, frame size rated current Inm 50A, rated impulse withstand voltage Uimp 6000V and connection from top and bottom, from bottom and top. This product is made in China and it is widely used in many places for its safety protection functions. This RCBO Type B is especially applicable for household and commercial buildings to protect against the risks associated with electric shock. It also provides protection against over-currents, over-voltages, short-circuits and other electrical hazards. It is especially suitable for industrial and outdoor applications, providing reliable protection against electrical faults. This product is also suitable for medical equipment, electric motors, power supplies and other sensitive electrical systems, as well as for general applications. With its superior performance and reliable protection, HAROK VRL22 2P,4P VRL11 VAL003 VKL003 VDL006 VRL01 VRL02 VRL03 VK007LE 1P-4P is the perfect choice for all your safety protection needs.

Technical Parameters:

Product Name RCBO Type B
Type Type B
Standard IEC/EN 61009-1, AS/NZS 61009.1
Frame size rated current Inm 50A
Poles 1P+N
Connection From Top And Bottom, From Bottom And Top
Rated Residual Operating Current 0.01A, 0.03A, 0.1A, 0.3A
Rated Residual Non-Operating Current 0.005A, 0.015A, 0.05A, 0.15A
Mechanical Life 2000
Electrical Life 2000

Customization:

RCBO Type B

Brand Name: HAROK

Model Number: VRL22 2P,4P VRL11 VAL003 VKL003 VDL006 VRL01 VRL02 VRL03 VK007LE 1P-4P

Place of Origin: CHINA

Rated Residual Non-Operating Current: 0.005A, 0.015A, 0.05A, 0.15A

Classified by Type of Instantaneous Tripping: Type B: (3 ~ 5) In, Type C: (5 ~ 10) In

Electrical Life: 2000

Type: Type B

Product Name: RCBO Type B

Residual Current Operated Circuit Breaker Type B

HAROK RCBO Type B is a Residual Current Operated Circuit Breaker which provides protection against electrical shocks and short circuits. It is classified by Type of Instantaneous Tripping, Type B: (3 ~ 5) In, Type C: (5 ~ 10) In. It has a Rated Residual Non-Operating Current of 0.005A, 0.015A, 0.05A, 0.15A and an Electrical Life of 2000. It is manufactured in China and is available in a variety of model numbers such as VRL22 2P,4P VRL11 VAL003 VKL003 VDL006 VRL01 VRL02 VRL03 VK007LE 1P-4P.

Support and Services:

RCBO Type B Technical Support and Services include:

  • Detailed product information, including product features, installation instructions, and troubleshooting tips.
  • Dedicated customer service representatives available to answer any questions.
  • Online product tutorials and webinars to help customers understand and utilize the product.
  • Regular software updates and maintenance releases.
  • Extended warranties and technical support contracts.

Packing and Shipping:

Packaging and Shipping for RCBO Type B:

  • The product is packed into a carton box and covered with bubble wrap.
  • The product is shipped through a reliable courier service.
  • The product is carefully inspected before shipment.
  • The product is marked with a unique serial number before shipment.

FAQ:

Q1: What is RCBO Type B?
A1: RCBO Type B is a residual current circuit breaker with overcurrent protection (RCBO) made by HAROK, with model number VRL22 2P,4P VRL11 VAL003 VKL003 VDL006 VRL01 VRL02 VRL03 VK007LE 1P-4P, which is made in China.
Q2: What is the function of RCBO Type B?
A2: RCBO Type B has two functions: it can protect people from electric shock by detecting leakage current and it can protect the electrical circuits from overload or short circuit.
Q3: What are the advantages of RCBO Type B?
A3: The advantages of RCBO Type B are: it is very sensitive to leakage current, it has high breaking capacity, it has long service life, it has low power consumption, it has high contact reliability, and it has a small size.
Q4: What applications can RCBO Type B be used in?
A4: RCBO Type B can be used in home appliances, such as refrigerators, air conditioners, washing machines, lamps, electric fans, etc.
Q5: What safety certifications does RCBO Type B have?
A5: RCBO Type B has passed the safety tests of CE, CB, and RoHS certifications.

Product tags
Send your message to this supplier
Send Now

VRL02 1P+N Mini RCBO Type B With Rated Current 6A, 10A, 16A, 20A, 25A, 32A, 40A, ,45A, 50A

Ask Latest Price
Brand Name :
HAROK
Model Number :
VRL02
Place of Origin :
CHINA
MOQ :
3000PCS
Payment Terms :
L/C, T/T
Poles number :
1P+N
Contact Supplier
VRL02 1P+N Mini RCBO Type B With Rated Current 6A, 10A, 16A, 20A, 25A, 32A, 40A, ,45A, 50A
VRL02 1P+N Mini RCBO Type B With Rated Current 6A, 10A, 16A, 20A, 25A, 32A, 40A, ,45A, 50A
VRL02 1P+N Mini RCBO Type B With Rated Current 6A, 10A, 16A, 20A, 25A, 32A, 40A, ,45A, 50A
VRL02 1P+N Mini RCBO Type B With Rated Current 6A, 10A, 16A, 20A, 25A, 32A, 40A, ,45A, 50A
VRL02 1P+N Mini RCBO Type B With Rated Current 6A, 10A, 16A, 20A, 25A, 32A, 40A, ,45A, 50A

Yueqing Vorax Electric CO.,LTD

Verified Supplier
3 Years
zhejiang
Since 2003
Business Type :
Manufacturer
Employee Number :
>100
Certification Level :
Verified Supplier
Contact Supplier