UPS lifepo4 battery pack, Ups Battery replacement 205V 14Ah High Discharge Rate RS485/Can Communication
Shenzhen Topband Battery Co., Ltd, a company professional to do LiFePO4 battery, which is founded in 1996 and listed in Shenzhen in 2007.There are over 300 R&D engineers and about 3,000 employees in the 70,000 square meters Topband industrial park.We can provide One-Stop Solution of new energy, from cell, BMS/PCM to battery pack assembling.
2. Product Performance
NO. | Items | Criteria | Testing method | |
2.1 | Rated Capacity | 14Ah | Rest for 1 hour after fully charged, then discharge with 0.33C current until the battery reaches the discharge cutoff voltage. Repeat above process for three times, if the discharge time is not less than 120 minutes, you can stop and define the Discharging current*time value (Ah) as battery capacity. | |
2.2 | Rated Energy | 2867Wh | ||
2.3 | Internal resistance | ≤400mΩ | 50% battery SOC state frequency of 1 KHZ ac resistance tester | |
2.5 | Cycle life (DOD100%) | ≥2000cycle | Discharge with the current of 0.33C until it can’t discharge, and then rest it for 1h. Charge the battery following CC(0.33C)/CV(14.6V) mode to full capacity, and then rest it for 1h. Repeat above process until full charged capacity is no more than 80% of normal value. Accumulated times is defined as cycle life. | |
2.6 | Discharge Temperature Characteristics | -20℃ | ≥70% | At 25±5℃ discharge the battery with the current of 0.33C to the cut-off voltage and record charge capacity. Store the battery at various temperatures for 2h and discharge the battery with 0.33C to the cut-off voltage. |
-0℃ | ≥80% | |||
25℃ | ≥100% | |||
55℃ | ≥95% | |||
2.7 | Charge Retention ability | Residual capacity≥80% | Charge the battery to full capacity and store it for 28days, and then discharge it with 0.33C to the cut-off voltage. | |
Recovery capacity≥90% |
3. Features
4. Specification(@Battery initial Temp25±5℃)
NO. | Items | Criteria | Remarks |
4.1 | Rated Capacity | 14Ah | |
Minimum Capacity | 10Ah | ||
4.2 | Energy | 2.867KWh | |
4.3 | Nominal Voltage | 208V | |
4.4 | Outgoing Voltage | ≥205V | |
4.5 | Internal resistance | ≤400mΩ | |
4.6 | Limited charge voltage | 233.6±5V | |
4.7 | Floating charge voltage | 220±5V | |
4.8 | Standard charge current | 14A | |
4.9 | Maximum charge current | 14A | |
4.10 | Standard discharge current | 20A | |
4.11 | Maximum discharge current | 80A | |
4.12 | Pulse discharge current | 160A for 3 s | |
4.13 | Discharge cut-off voltage | 162.5V | |
4.14 | Dimension | Length: 439±3mm | |
Width: 82±3mm | |||
Height: 656±3mm | |||
4.15 | Weight | Approx: 38±0.5Kg | |
4.16 | Operating Temperature | Charging:0~45℃ | |
Discharging:-20~60℃ | |||
Recommended operating temperature:15℃~35℃ | |||
4.17 | Self-discharge rate | Residual capacity:≤3%/month;≤15%/years | |
Reversible capacity:≤1.5%/month;≤8%/years | |||
4.18 | Storage Temperature & Humidity Range | Less than 1 month:-20℃~35℃,45%RH~75%RH | |
Less than 3 months:-10℃~35℃,45%RH~75%RH | |||
Recommended storage environment: 15℃~35℃,45%RH~75%RH | |||
Long time storage: If the battery need be stored for a long time, the voltage should be 52.8V(50%SOC), and stored in the condition as storage proposal. It need at least one charge & discharge cycle every six months |
5. Transportation
1) Based on the character of cell, proper environment for transportation of LiFePO4 battery pack need to be created to protect the battery.
2) Battery should be stayed in the warehouse 15℃~35℃ where it’s dry, clean, shade, and well-ventilated.
3) The battery should be stored in 50% SOC during transportation.
4) The battery need to be charged every 6 months if out of use
5) Keep the battery against dropping, turning over and serious stacking during loading.
6. Warning & Tips
Please read and follow the specification and caution remarks on battery surface before use the battery. Improper use may cause heat, fire, rupture, damage or capacity deterioration of the battery. Shenzhen Topband Battery Co., Ltd. Describes is not responsible for any accidents caused by the usage without following our specification.