400V 300kW Automatic Portable Load Bank In High Performance and Grey Colour
Introduction
AC400-300kW Load Bank can accurately test output power and load capacity for all kinds of generators, generator sets for all main electrical parameters including testing the dynamic parameters.
Applications
Kaixiang load banks operate at the actual output voltage of medium voltage generators and therefore do not require large step-down transformers, which reduces the overall package size and installation costs. Kaixiang’s quality system is certified to meet ISO9001:2015 standards. Kaixiang AC load banks certified by CE certificate.
Kaixiang has more than 20 years of professional experience in testing and commissioning of generators, batteries and UPS. Our high capacity load banks are exported to more than 20 countries around the globe in a wide variety of applications such as military ships, offshore platforms, data centre, power stations, generator manufacturers and research institutes.Its customers widely distributed in America, Mexico, Netherlands, Australia, Singapore, Israel, Poland, Saudi Arabia, UAE, Egypt, Indonesia, Malaysia,Vietnam, The Philippines, Cambodia, Sudan etc.
Technical specification
Technical Parameters | |
Rating Voltage/Frequency | 400VAC 50Hz,3phase 4 wire, |
Max Load Power | Resistive Load: 300kW |
Load Step | Resistive Load.11steps; 1,2,2,5,10,10,20,50,100,100kW. |
Power Factor | 1 |
Load Tolerance(each step) | ±5% |
Load Tolerance(overall) | ±3% |
Display accuracy | 0.5 grade |
Control Power Supply | External 400VAC, 3phase 4wire 50Hz, |
Wire Connection | Load Power Supply Input——Copper bar (star connection) Control power supply input——Connector bar |
Communication Interface | RS232 and RS485 |
Protection Grade | Control Part: IP55; Protection of Resistor Cabin:IP 55 when stock state,IP21 when operation state |
Insulation Class | F |
Duty Cycle | Continuous |
Cooling | Forced air cooling, horizontal air inlet and air outlet |
Transportation | Hoisting, there are lifting lug in top of case and wheel castors on the bottom |
Chassis color | Gray(RAL7035) |
Size | Approximately; 1980mm*900mm*1500mm(without wheel castors)(Width *Length *Height) |
Weight | Approximately 500kg |
Operating Environment Parameter | |
Ambient Temperature | -10℃~+50℃ |
Relative Humidity | ≤95% |
Altitude | ≤2500 meters |
Atmospheric Pressure | 86~106kPa |
Main features
Load/unload with one key: Whether manual control and software control, user can preset the power, then press load master button. Load bank loaded according to preset power to avoid load fluctuation during the power changing.
Control Pattern: user can choose local control and intelligent control.
Local Control: There is local control panel with several power steps, user can load/unload by button.
Intelligent Control: Through data processing software in PC, user can make automatic load, to display, record and manage the testing data, to form curves, tables, also to print them.
Control Pattern interlock, there is control pattern switch, when choose one control pattern, operation of other pattern is invalid, avoid the clash.
Local meter display data: local meter can display 3 phases voltage, current, active power, frequency and so on.