Ocean Engineering Automatic 400V 105RLC Dummy Electrical Load Bank
Product Description
According to the special requirements of users on site, in the agreement the technical standards of AC440-105-RLC Load Bank (hereinafter referred to as "system") and its accessories are proposed including their function, performance, usage, structure, installation and test to provide users with a high efficient and reliable choice, in order to meet the need for generator load test.
Technical Parameter
Rating Voltage/Frequency | 400VAC/50Hz, 3 phase 4 wire, |
Max Rated power | Resistive load: 45kW Inductive load:30 kva Capacitive load:30kvar |
Load Step | Resistive load: per phase 16kW A:0.1,0.2,0.2,0.5,1.2.2.5.5kw B :0.1,0.2,0.2,0.5,1.2.2.5.5kw C:0.1,0.2,0.2,0.5,1.2.2.5.5kw
Inductive load: per phase 11kva A:0.1,0.2,0.2,0.5,1.2.2.5.5kva B :0.1,0.2,0.2,0.5,1.2.2.5.5kva C:0.1,0.2,0.2,0.5,1.2.2.5.5kva
Capacitive load:per phase 11kvar A:0.1,0.2,0.2,0.5,1.2.2.5.5kvar B :0.1,0.2,0.2,0.5,1.2.2.5.5kvar C:0.1,0.2,0.2,0.5,1.2.2.5.5kvar |
PF(Power Factor) | 1 |
Load Tolerance (each step) | ±5% |
Load Tolerance(overall) | ±3% |
Display Precision | 0.5 class |
Control Power | 220VAC/50Hz, |
Wire Connection | Load power supply input——Copper bar (star coupling) Control power supply input——Connector-bar |
Communication Interface | RS485,RS232 |
Casing Dimensions and Cooling | about 1000*1500*1600mm (length*width*height) Forced air cooling,Horizontal inlet air,Vertical cooling |
Weight | About 500kgs/set |
Transportation | Hoisting, there are lifting lug in top of casing |
Casing Color | Grey(RAL7035) |
Ambient Temperature | -10℃~+50℃ |
Relative Humidity | ≤95% |
Altitude | ≤2500 meter |
Atmospheric Pressure | 86~106kPa |
Contactor | Schneider |
Fuse | DELIXI |
MCU | INFINEON |
Data processing software | Kaixiang(self-developed) |
Alloy Resistance | Kaixiang(self-developed) |
Product Advantage
1. The most patent technology and scientific research awards gainer in China.
2. Advanced detection method and strict inspection procedure build the qualified quality.
3. Customized production meet the individual requirement.
4. Prompt delivery & excellent after sales service.
5. Cooperate with many well-known enterprise, offer OEM and ODM service to world famous brands.
6. Certified with China Classification Society (CCS) and ISO9001:2008 Quality Certificate.
Application
1. Manufacturers of standby power generators commonly use load banks to test and tune newly assembled units
2. generator has been set up in a test cell within the factory, a test engineer uses the load bank to apply a discrete, selectable electrical load to the generator and measure the response stability and endurance.
3. During this process, the test engineer calibrates and adjusts the generator performance to ensure it meets the intended product specifications and tolerances.