New Design 2100KW Electrical Load Bank Testing On Generator Sets
Product Description
load bank are available in stationary type for permanent installation or portable type with lifting rings, castors. Larger load banks, typically above 2100KW, are based on an ISO container construction. Special finishes including custom paint colors and stainless steel casings can be supplied.
Technical Parameter
Rating Voltage/Frequency | 400VAC/50Hz, 3 phase 4 wire, line voltage 400V, phase voltage 230V |
Rated Load Power | Resistive load: 2100kW |
Installed Capacity | Resistive load: 2100kW |
Load Step | 1,2,2,5,10,10,20,50,100,100,200kW*9, total 19 steps, min step load: 1kW for each set of 2100kW load bank. |
PF(Power Factor) | 1 |
Load Tolerance (each step) | ±5% |
Load Tolerance(overall) | ±3% |
Display Precision | 0.5 class |
Control Power | 380VAC/50Hz, 3 phase 4 wire, |
Wire Connection | Load power supply input——Copper bar (star coupling) Control power supply input——Connector-bar |
Insulation | F |
Protection Grade | IP21 |
Way of Working | Continuous Working |
Casing Dimensions and Cooling | about 6058*2438*2591mm (length*width*height) Forced air cooling,Horizontal inlet air,Vertical cooling |
Weight | About 4200kgs/set |
Transportation | Hoisting, there are lifting lug in top of casing |
Casing Color | Grey(RAL7035) |
Ambient Temperature | -10℃~+50℃ |
Relative Humidity | ≤95% |
Altitude | ≤2500 meter |
Atmospheric Pressure | 86~106kPa |
Contactor | Schneider |
Fuse | DELIXI |
MCU | INFINEON |
Data processing software | Kaixiang(self-developed) |
Alloy Resistance | Kaixiang(self-developed) |
Product Advantage
1. User can press the emergency stop button in the panel to unload immediately when the load bank is abnormal while working.
2. Over-load: Automatic load dump and give alarm when voltage is over safety thresholds.
3. Over-heat protection: Automatic load dump and give alarm when temperature is over safety thresholds.
4. Short Circuit Protection: Fuse could avoids damage to equipment when short circuit or current overload.
Application
Load Banks are used with Engine Generators, Battery Systems, UPS Systems, Inverters, Ground Power Units, Auxiliary Power Units, Aircraft Power Generators, Wind Generators, and Hydro Generators.