AC400-550kW Adjustable Load Bank In 3 phase 4 wire With Frequency 50 HZ
Introduction
(1) This system, which is of independent research and development of electricity load test equipment by our technology, combining dry load module with the automatic measurement and control module, can accurately detect all kinds of generator output power and load capacity, full load and overload test.
(2) The system consists of 1 sets of 500kW Resistive load bank. The System is made up of two parts of measurement and control and load, mainly including AC dry load, automatic data acquisition system, automatically loading and unloading control system, the cooling device, auxiliary control, PC software and so on.
Application
1. Ups system testing
2. Load optimization in prime power applications
3. Factory testing of turbines
4. factory testing of engine generator sets
5. To reducewet stacking problems
6. Periodic excercising of stand-by engine generator sets
Technical specification
System Parameters | |
Rated Voltage/ Frequency | AC 400V/50Hz, 3 phase 4 wire |
Max Load Power | Resistive Load: 550kW |
Load Step | 1,2,2,5,10,20,20,50,100,100,200kW, total 11 steps, can arbitrary combination between 1KW~510KW, min load precision is 1kw |
Power Factor | 1 |
Load Tolerance(each step) | ±5% |
Load Tolerance(overall) | ±3% |
Display Precision | 0.5 class |
Control Power Supply | AC380V/50Hz 3 phase 4 wire |
Wire Connection | Load Power Supply Input——Copper bar (star connection) Control power supply input——Aviation plug |
Insulation Class | F class |
Duty Cycle | Continuous |
Cooling | Forced air cooling,Horizontal inlet air,upwards outlet |
Transportation | Hoisting, with lifting lug on the top and castors at the bottom of casing |
Casing color | Grey (RAL7035) |
Dimension | About 1460 mm×1980mm×1800mm(L×W×H) |
Weight | About 900kg |
Operating Environment Parameter | |
Ambient Temperature | -10℃~+50℃ |
Relative Humidity | ≤95% |
Altitude | ≤2500m |
Atmospheric Pressure | 86~106kPa |
Load testing: Can load power that within the rated power, test and display stable state 3 phases voltage, current, active power, frequency, working time, etc of generator sets.