westerbeke 300 KW testing equipment for generator ups transformer testing
Introduction
AC400-300KW Resistive Load Bank. The system accurately test output power and load capacity of all kinds of generators, main electrical parameters including the dynamic parameters tested.
Application
Technical specification
Technical Parameters | |
Rating Voltage/Frequency | AC 400V/50Hz, 3 phase 4 wire |
Max Load Power | Resistive Load: 310kW |
Load Step | Resistive Load:10 steps; 1, 2, 2, 5, 10, 20, 20, 50, 100,100kW |
Power Factor | 1 |
Load Tolerance(each step) | ±5% |
Load Tolerance(overall) | ±3% |
Display Precision | 0.5 class |
Control Power Supply | Input400VAC 3 phase 4 wire 50hz |
Wire Connection |
Load Power Supply Input——Copper bar (star connection) Control power supply input——Connector bar |
Communication Interface | RS485 (2), RS232 (1) |
Insulation Class | F |
Working Mode | Continuous Working |
Cooling | Forced air cooling,Horizontal inlet air,Horizontal outlet |
Transportation | Hoisting, there are lifting lug in top of case and wheel castors in bottom |
Chassis color | Black&White(RAL7035) |
Dimension |
Approximately; 1250*1550*1680 (Width *Length *Height) |
Operating Environment Parameter | |
Ambient Temperature | -10℃~+50℃ |
Relative Humidity | ≤95% |
Altitude | ≤2500 meters |
Atmospheric Pressure | 86~106kPa |
Communication pattern: Intelligent control use photoelectric isolated RS485 interface connect to PC, with great anti-interference performance to make system control stable. Also user can use USB or RS232 through converter.
Load pattern: Manual Load or Automatic Load.
Manual Load: Input power, system will load according to preset power.
--Automatic load: user can preset power and length of working time of several load periods, as per 0%→25%→50%→75%→100% or 110% to make testing.
Parallel testing: when several load bank work in parallel, use can make parallel testing via software, can display, record parameters of every load bank and whole system parameter of parallel operation.
--Real-time parameter: through software to display voltage, current, power, power factor, frequency and time, etc.
Security monitoring and control: monitor working state of the load bank by watching software light, when abnormally stop and protect, it can show the reason.
Data save and query: all the test data is saved in the software, easy to query in the history testing data.
Graphical display: show real-time or history testing data, and support to print curve and graph as follows:
1) Graphs of real-time voltage, current, frequency and power; 2) Voltage graph
3) Current graph; 4) Power graph; 5) Frequency graph; 6) Power factor graph
Data format: all the curves and graphs can be outputted as".doc"format, testing data can be outputted as ”.xls” format, and can be printed.