125KVA Inductive Load Bank With 86 ~106 KPa Atmospheric Pressure
Product description
The system consists of 1 sets of 125KVA Resistive/Inductive load bank. The resistive power is 100kW. The System is made up of two parts of measurement and control and load, mainly including the outdoor type dry load, automatic data acquisition system, automatically loading and unloading control system, the cooling device, auxiliary control, remote controller and PC software and so on.
Technical Parameter
Rating Voltage/Frequency | 400VAC/50Hz, 3 phase 4 wire, |
Voltage range | 400v 50hz ±10% |
Max Rated power |
Apparent Power: 125kVA |
Load Resolution |
Resistive load:1.2.2.5.10.10.20.50kw |
Load Tolerance (each step) | ±5% |
Load Tolerance(overall) | ±3% |
Display Precision | 0.5 class |
Control Power | AC380VAC/50Hz,3 phase 4 wire |
Wire Connection |
Load power supply input——Copper bar (star coupling) |
Communication Interface | RS485, |
Casing Dimensions and Cooling | about 1550*1250*1680mm (length*width*height) Forced air cooling,Horizontal inlet air,Vertical cooling |
Weight | About 530kgs/set |
Transportation | Hoisting, there are lifting lug in top of casing |
Casing Color | Grey(RAL7035) |
Ambient Temperature | -10℃~+50℃ |
Relative Humidity | ≤95% |
Altitude | ≤1500 meter |
Atmospheric Pressure | 86~106kPa |
Contactor | Schneider |
Fuse | DELIXI |
MCU | INFINEON |
Data processing software | Kaixiang(self-developed) |
Alloy Resistance | Kaixiang(self-developed) |
Product Advantage
Design of intelligent test system of generator unit, production and services are in strict accordance with the GB/T19001-2008 "quality management system" requirements, and refer to the following standards. Some standards may not be suitable for practical applications, the technical agreement production plan system finally to agreed prevail.
Application
Large generator system testing in ocean engineering, drilling facilities,ship construction
etc field
Factory testing for generator, static voltage characteristic test, speed characteristic test;
Marine generator overload protection test,parallel operation test,reverse power and reverse current protection test
Assist shipyard in mooring test,sea trial test
Assist with the acceptance of the vessel generator test