Power bank 2500 KW AC Electric Load Banks For Testing Generators UPS
Product description
(1) According to the special requirements of users on site, in the agreement the technical
standards of AC425-2500kW Intelligent Load Bank(hereinafter referred to as "system") and its accessories are proposed including their function, performance, usage, structure, installation and test to provide users with a high efficient and reliable choice, in order to meet the need for generator load test.
(2) The system consists of 1 sets of 2500kW load bank. The resistive power is 2500kW. The System is made up of two parts of measurement and control and load, mainly including the outdoor type dry load, automatic data acquisition system, automatically loading and unloading control system, the cooling device, auxiliary control, remote controller and PC software and so on.
Technical Parameter
System Parameter | |
Rating voltage/frequency | AC 3 phase 4 line, 425V/50Hz |
Max Load Power | Resistive Load: 2500kW |
Load Resolution | Resistive Load: 21 steps, 1kW,2kW,2kW,5kW,10kW,10kW,20kW,50kW,100kW,100kW,200kW, 200kW, 200kW, 200kW, 200kW,200kW, 200kW, 200kW, 200kW, 200kW, 200kW |
Power Factor | 1 |
Load Tolerance (each step) | ±5% |
Load Tolerance (overall) | ±3% |
Fan &Control Voltage | External AC 3 phase 4 line,425V/50Hz |
Wire Connection | Load bank input——Copper bar (star coupling ”Y”) Control power input——Connector-bar |
Communication Interface | RS485,RS232 |
Insulation | F |
Max Protection Grade | IP54 |
Duty Cycle | Continuous |
Cooling | Forced air cooling, by Axial Fan; horizontal inlet air, vertical exhaust cooling |
Enclosure | Container type,with a ladder, air inlet and outlet with mesh enclosure and protection door |
Internal Lighting | Adequate internal lighting will be provided |
Transportation | Hoisting, there are lifting lug in top of casing |
Color | Grey RAL7035 or as required |
Dimensions | About 6058mm×2350mm×2591mm(L×W×H) |
Operating Environment Parameter | |
Ambient Temperature | -10℃~+50℃ |
Relative Humidity | ≤95% |
Atmospheric Pressure | 86~106kPa |
Brands of Main Components | |
Contactor | Schneider |
Fuse | Miro |
PLC | Siemens |
Alloy Resistor | (self-developing) |
Data Processing Software | (self-developing) |
Overheating Protection: temperature is over the safe threshold value, system unload automatically and give an alarm.
Smoke Fog Protection: If there is smoke fog in the container, system cut off load automatically and give an alarm.
Overload protection with fan: when any fan cannot normally work, the load bank can unload automatically and give an alarm.
Emergency Stop: manually press the Emergency Stop switch on the panel, then load bank is in locked state, and cannot do any operation.
Protection Switch: some protection with switch, when misinformation or in special need, user can close the corresponding protection function temporarily.
Safety Monitor: through indicator lights on main interface, user can monitor system state. When system abnormally stop and protect, software interface prompt the cause immediately.
Short Circuit Protection and Over Current Protection: when short circuit, fuses in the load bank can insure to unload automatically.
Application
Large generator system testing in ocean engineering, drilling facilities,ship construction etc field
Factory testing for generator, static voltage characteristic test, speed characteristic test;
Marine generator overload protection test,parallel operation test,reverse power and reverse current protection test