Liquid Cooling Solution For Crypto-currency Computers Liquid Immersion Cooling Tanks
Data center challenges with one immersion cooling solution.
The global datacentre industry is one of the fastest growing technology driven industries. With emerging digital technologies, for instance artificial intelligence, data analytics, virtual reality, IoT and advanced cloud services we could say we are on a wave of high performance computing.
Obviously datacentres are necessary for digital economies, however datacentres are dealing with significant challenges, for instance they are facing boundaries regarding floorspace, access to (renewable) energy, cooling costs, complexity and cost of build.
The next hardware component generations facilitating the emerging digital technologies are high powered and require high density hardware platforms. This results in a situation whereby the traditional datacentre model does not fit with the technology it should be facilitating. In addition, datacentres are generating energy (hot air) which is consistently wasted as it is impossible to transport to heat users in an efficient and cost friendly way.
Shenglin can offer liquid immersion cooling system. Large-scale cooling equipment is not required, so the system reduces the total power consumption for the server system as a whole by about 40% compared to existing air cooling systems. This dramatic reduction of power consumption allows customers to approximately double the server density in the same installation space.
Shenglin dry cooler is the most cost-effective way to remove heat and a necessary component of the immersion cooling system, We designed a full range of immersion optimized dry coolers. From 5kW single fan unit to the V-shaped 48-921kW dry coolers. Made in China, sized to your needs.
Features
Air discharge direction | ![]() |
Performance ranges | Cooling capacity: from 5 to 649 kw Air volume: from 2828 to 263503 m3/h Sound pressure level: from 31 to 69 dB A(10m) Dry coolers:customized on demand |
High efficiency heat exchanger | Capacity designs for maximizing the heat transfer relative to the energy consumption of the fan. Tube and tube coupling design for low pressure drop in the coil on the media sides(maximum 100KPa at water designing condition). Our thermodynamic and aerodynamic designing software is long year tested and proved in Germany |
Fan | Only choose low specific energy consumption fans. Fan nozzle designs for maximum air flow and air throw. Our fans from the world`s leading manufacturer are practically proved to be reliable in operation and long lasting. Motor: protection class IP 54 and insulation class F. Voltage:400V/3N/50Hz Air separator for each fan. |
Testing | Heat exchangers are supplied clean and tested at a pressure of 30 bars |
Options | Coil design refrigerant: water, oil, glycol. Multiple circuits. Sub-cooling circuits. Stainless steel or aluminum casing. Coated aluminum or copper fins. Explosion ploof motor. Customized fin spacing.
|
Technical parameter
Dry cooler D4 series parameter(fin space 2.1mm)
Type | D4-428- 10X800 | D4-488- 10X800 | D4-510- 10X800 | D4-520- 12X800 | D4-591- 12X800 | D4-617- 12X800 | D4-724- 14X800 | D4-792- 16X800 | |||||||
Capacity | Water | 35℃ outdoor temp. | Inlet | 45℃, | KW | 427.6 | 488.1 | 509.9 | 519.9 | 590.7 | 616.7 | 723.6 | 791.6 | ||
outlet | 40℃ | ||||||||||||||
20% Glycol | Inlet | 45℃ | 411 | 476.6 | 498.6 | 503.5 | 579.2 | 605.5 | 712.4 | 777.2 | |||||
outlet | 40℃ | ||||||||||||||
Medium | Water flow | M3/h | 74.3 | 84.9 | 88.7 | 90.4 | 102.7 | 107.2 | 125.8 | 137.6 | |||||
Pressure drop | kPa | 28 | 60 | 48 | 43 | 99 | 78 | 99 | 99 | ||||||
Air flow | M3/h | 216938 | 202183 | 193538 | 260320 | 242613 | 232238 | 270940 | 323168 | ||||||
Fan motor(400V/3N/50HZ) | W | 18000 | 18000 | 18000 | 21600 | 21600 | 21600 | 25200 | 28800 | ||||||
A | 38 | 38 | 38 | 45.6 | 45.6 | 45.6 | 53.2 | 60.8 | |||||||
Fan | No X φ | 2X5X800 | 2X5X800 | 2X5X800 | 2X6X800 | 2X6X800 | 2X6X800 | 2X7X800 | 2X8X800 | ||||||
Sound pressure level | dB(A) | 60 | 60 | 60 | 62 | 62 | 62 | 64 | 66 | ||||||
10m | |||||||||||||||
Dimension | L | mm | 6270 | 6270 | 6270 | 7470 | 7470 | 7470 | 8670 | 9870 | |||||
W | mm | 2520 | 2520 | 2520 | 2520 | 2520 | 2520 | 2520 | 2520 | ||||||
H | mm | 2000 | 2000 | 2000 | 2000 | 2000 | 2000 | 2000 | 2000 | ||||||
Inlet φ | mm | 2X4” | 2XDN125 | 2XDN125 | 2XDN125 | 2XDN125 | 2XDN125 | 2XDN125 | 2XDN125 | ||||||
Inlet φ | mm | 2X4” | 2XDN125 | 2XDN125 | 2XDN125 | 2XDN125 | 2XDN125 | 2XDN125 | 2XDN125 | ||||||
Product weight(empty) | kg | 2159 | 2250 | 2327 | 2480 | 2568 | 2741 | 2947 | 3342 |
Why choose us:
1) We can help buyers design specific products or produce products according to buyers' design
2) We can print logo according to buyers' requirement
3) We has exported to many countries,such as Singapore, Philippines, Vietnam, Argentina, Peru, Mongolia, Hong Kong, UAE,Russia, Poland etc.
4) Design term:We have professional design team.
5) Professional factory: We are manufacturer, specializing in manufacturing heat exchangers for over 16years, competitive price with good quality.
6) Rapid response to your needs: We will reply within 24 hours after receiving you letter. If you have urgent thing, welcome to call us.
7) The Most Efficient Service, Best Quality and Excellent Reputation.