Customized Dry Air Cooling System For Injection Moulding Machines
Features
Dry coolers use ambient air to cool process fluids. Multiple units can be employed to handle even greater heat loads. Configuration choices include horizontal or vertical air discharge, single or double row fans, and vertical, horizontal or V mounted coils. Units can have multiple circuits, multiple passes and can be configured to be piped in series or parallel. The rugged, weather-proof design is manufactured with corrosion-resistant galvanized steel sheet, finished with high quality polyurethane paint. Standard cooling coils consist of copper tubes and aluminum fins, which are coupled with high efficiency, low noise fans. A variety of optional fan controls can be provided, including step controls and variable speed drives in single- and three-phase voltages to match your electric power supply.
Technical parameter
Dry cooler D2 series parameter(fin space 2.1mm)
Type | D2-148- 4x630 | D2-166- 4x630 | D2-175- 4x630 | D2-228- 6x630 | D2-250- 6x630 | D2-276- 6x630 | D2-310- 8x630 | D2-343- 8x630 | D2-364- 8x630 | D2-392- 10x630 | |||
Capacity | Water | KW | 147.99 | 165.85 | 175.21 | 227.85 | 250.42 | 276.53 | 309.85 | 342.73 | 364.07 | 391.99 | |
20% Et. Glycol | KW | 142.42 | 161.57 | 170.91 | 219.09 | 244.69 | 270.22 | 301.18 | 333.55 | 354.64 | 383.3 | ||
Air flow | M3/h | 76459 | 74341 | 72134 | 114686 | 111511 | 108188 | 152911 | 148675 | 144255 | 191136 | ||
Fan | No. X φ | 2x2x630 | 2x2x630 | 2x2x630 | 2x3x630 | 2x3x630 | 2x3x630 | 2x4x630 | 2x4x630 | 2x4x630 | 2x5x630 | ||
Fan motor | A | 20.4 | 20.4 | 20.4 | 30.6 | 30.6 | 30.6 | 40.8 | 40.8 | 40.8 | 51 | ||
400/3N/50HZ | |||||||||||||
Sound pressure level | dB(A)10m | 64 | 64 | 64 | 66 | 66 | 66 | 67 | 67 | 67 | 68 | ||
Dimension | L | mm | 2186 | 2186 | 2186 | 3250 | 3250 | 3250 | 4250 | 4250 | 4250 | 5250 | |
H | mm | 1874 | 1874 | 1874 | 1874 | 1874 | 1874 | 1874 | 1874 | 1874 | 1874 | ||
D | mm | 2100 | 2100 | 2100 | 2100 | 2100 | 2100 | 2100 | 2100 | 2100 | 2100 | ||
D1 | mm | 2000 | 2000 | 2000 | 2000 | 2000 | 2000 | 2000 | 2000 | 2000 | 2000 | ||
L1 | mm | 963 | 963 | 963 | 963 | 963 | 963 | 963 | 963 | 963 | 963 | ||
L2 | mm | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | ||
L3 | mm | 1963 | 1963 | 1963 | 2963 | 2963 | 2963 | 3963 | 3963 | 3963 | 4963 | ||
Connections inlet φ | mm | 2XDN50 | 2XDN65 | 2XDN65 | 2XDN65 | 2XDN80 | 2XDN80 | 2XDN80 | 2XDN80 | 2XDN100 | 2XDN100 | ||
Connections onlet φ | mm | 2XDN50 | 2XDN65 | 2XDN65 | 2XDN65 | 2XDN80 | 2XDN80 | 2XDN80 | 2XDN80 | 2XDN100 | 2XDN100 | ||
Product weight(empty) | kg | 769 | 811 | 853 | 1134 | 1197 | 1261 | 1498 | 1589 | 1673 | 1864 |
Reference:
Dry cooler case | |
Case 1: used in chemical plant. | Case 2: used in chemical plant. Refrigerant: ethylic acid(flow: 372 ton/h)
|
![]() ![]() | ![]() ![]() |
Case 3: used in communication station as air conditioner outdoor unit in China. | Case 4: used in communication station as air conditioner outdoor unit
|
![]() | ![]() |