Wet-Dry Coolers With Direct Water Spray System For Bitcoin Two-phase Liquid Cooling System
Two-phase liquid cooling:
The cooling liquid undergoes a phase change in the process of circulating heat dissipation. The cooling liquid takes away the heat from the server and then undergoes a phase change gasification. The gaseous cooling liquid is condensed by the condenser and becomes liquid again and returns to the liquid cooling tank; the cooling liquid can use 3M electronics The boiling point of the coolant FC-72 and FC-72 is above 50℃. In this case, the temperature of the water in the condensing coil does not need to be too low. The use of a dry cooler can meet the heat exchange requirements and take away the heat. The two-phase liquid cooling has a high heat transfer efficiency due to the phase change of the electronic cooling liquid. The disadvantage is that during this phase change, the electronic fluorinated liquid will escape during the vaporization process, so there is a certain degree of tightness of the container. However, it should not be too sealed to prevent the cooling system from being interrupted and the cylinder explosion event, so certain safety facilities need to be set up.
Features
1. High efficiency heat exchanger: capacity designs for maximizing the heat transfer relative to the energy consumption of the fan.
2. Tube and tube coupling design for low pressure drop in the coil on the media sides(maximum 100KPa at water designing condition).
3. Our thermodynamic and aerodynamic designing software is long year tested and proved in Germany.
4. Fan: only choose low specific energy consumption fans.
5. Fan nozzle designs for maximum air flow and air throw.
6. Our fans from the world`s leading manufacturer are practically proved to be reliable in operation and long lasting.
7. Motor: protection class IP 54 and insulation class F.
8. Air separator for each fan.
9. We facilitate you to have a long lasting and low maintainance operation.
10. Durable material and rigid enclosure with hard gloss powder coated finish.
11. Protective enclosure for both manifolds and U-bends.
12. Unit design for outdoor installation. 100% leakage tested at 31bar.
Options
A. Coil design refrigerant: water, oil, glycol.
B. Multiple circuits.
C. Sub-cooling circuits.
D. Stainless steel or aluminum casing.
E. Coated aluminum or copper fins.
F. Explosion proof motor.
G. Customized fin spacing.
Technical parameter
Dry cooler D3 series parameter (fin space 2.1mm)
Type D3- | 042-1X800 | 046-1X800 | 051-1X800 | 087-2X800 | 094-2X800 | 103-2X800 | 125-3X800 | 146-3X800 | D53-3X800 | 175-4X800 | 188-4X800 | ||||
Capacity (KW) | Water | 35℃ outdoor temp. | Inlet | 45℃ | 42.1 | 46.1 | 50.6 | 87.3 | 93.6 | 102.9 | 124.9 | 145.9 | 153.3 | 174.5 | 187.9 |
outlet | 40℃ | ||||||||||||||
20% Glycol | Inlet | 45℃ | 40.8 | 45.1 | 49.7 | 84.5 | 91.8 | 100.9 | 119.4 | 143 | 150.4 | 168.9 | 184.3 | ||
outlet | 40℃ | ||||||||||||||
Medium | Water flow | M3/h | 7.3 | 8 | 8.8 | 15.2 | 16.3 | 17.9 | 21.7 | 25.4 | 26.6 | 30.3 | 32.7 | ||
Pressure drop | kPa | 49 | 69 | 97 | 48 | 98 | 93 | 21 | 97 | 89 | 48 | 98 | |||
Air flow | M3/h | 21454 | 20531 | 19696 | 42906 | 41061 | 39390 | 64364 | 61585 | 59087 | 85811 | 82120 | |||
Fan motor(400V/3N/50HZ) | W | 1800 | 1800 | 1800 | 3600 | 3600 | 3600 | 5400 | 5400 | 5400 | 7200 | 7200 | |||
A | 3.8 | 3.8 | 3.8 | 7.6 | 7.6 | 7.6 | 11.4 | 11.4 | 11.4 | 15.2 | 15.2 | ||||
Fan | No X φ | 1x1 x800 | 1x1 x800 | 1x1 x800 | 1x2 x800 | 1x2 x800 | 1x2 x800 | 1x3 x800 | 1x3 x800 | 1x3 x800 | 2x2 x800 | 2x2 x800 | |||
Sound pressure level | dB(A) | 50 | 50 | 50 | 51 | 51 | 51 | 53 | 53 | 53 | 54 | 54 | |||
10m | |||||||||||||||
Dimension | L | mm | 2000 | 2000 | 2000 | 3800 | 3800 | 3800 | 5600 | 5600 | 5600 | 3800 | 3800 | ||
W | mm | 1084 | 1084 | 1084 | 1084 | 1084 | 1084 | 1084 | 1084 | 2108 | 2108 | 2108 | |||
H | mm | 1328 | 1328 | 1328 | 1328 | 1328 | 1328 | 1328 | 1328 | 1328 | 1328 | 1328 | |||
A | mm | 1728 | 1728 | 1728 | 3528 | 3528 | 3528 | 5328 | 5328 | 5328 | 3528 | 3528 | |||
B1 | mm | -- | -- | -- | 1764 | 1764 | 1764 | 1776 | 1776 | 1776 | 1764 | 1764 | |||
B2 | mm | -- | -- | -- | 1764 | 1764 | 1764 | 1776 | 1776 | 1776 | 1764 | 1764 | |||
B3 | mm | -- | -- | -- | -- | -- | -- | 1776 | 1776 | 1776 | -- | -- | |||
B4 | mm | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | -- | |||
X | mm | 997 | 997 | 997 | 997 | 997 | 997 | 997 | 997 | 997 | 2021 | 2021 | |||
Inlet φ | mm | 2” | 2” | 2” | 2 1/2” | 2 1/2” | 2 1/2” | 3’ | 3’ | 3’ | 4” | 4” | |||
Inlet φ | mm | 2” | 2” | 2” | 2 1/2” | 2 1/2” | 2 1/2” | 3’ | 3’ | 3’ | 4” | 4” | |||
Product weight(empty) | kg | 225 | 233 | 241 | 357 | 373 | 392 | 796 | 527 | 749 | 812 | 1062 |
We can OEM design dry coolers.
Tell us the datas as following:
A. Required BC888·s inlet temperature?
B. Required BC888·s outlet temperature?
C. BC888 flow?
D. Ambient temperature?
E. Supply power(voltage-Hz-phase)
G. Any other requirements ?
Packing:
![]() | ![]() |
![]() | ![]() |