Specifications
Model Number :
OD-22
Place of Origin :
China
Brand Name :
ALEPH
Certification :
CE ISO
MOQ :
1pcs
Price :
Negotiable
Packaging Details :
Packaging Details:gift box/color box packaging or according t
Delivery Time :
25-30 days
Payment Terms :
TT IN ADVANCE
Relay Hold Time :
0.5-64 seconds
LED Indication :
Red
Supply Voltage :
12-24VDC or VAC .
Supply Current :
18-30mA@12-24VDC,45-80mA@12-24VAC
Detection Type :
Passive infrared
Operating Temperature :
- 14°F to 131°F(- 10° C to 55°C)
Weight :
0. 4lb( 0. 18kg)
Dimensions :
6.53"Wx1. 57"Hx1. 53"D( 166x40x39mm)
Description

REQUEST-TO-EXIT Passive Infrared Sensor 0-95% non-condensing Humidity REQUEST-TO-EXIT Passive Infrared Sensor

1. SPECIFICATIONS
Supply Voltage 12-24VDC or VAC .
Supply Current 18-30mA@12-24VDC,45-80mA@12-24VAC
Relay Output 2C Contact(N.C/N.O) , 24VDC 1A Max.
Detection Type Passive infrared
Relay Hold Time 0.5-64 seconds
LED Indication Red
Range Coverage 12x5 ft at 7ft high,30x12 ft at 15 ft high(Adjustment )
Operating Temperature - 14°F to 131°F(- 10° C to 55°C)
Weight 0. 4lb( 0. 18kg)
Humidity 0-95% non-condensing
Dimensions 6.53"Wx1. 57"Hx1. 53"D( 166x40x39mm)

DESCRIPTION
The OD-22 passive infrared Sensor is specifically designed for to-exit applications , Standard OD-22 include qualified motion analysis. The OD-22 may be mounted toframe header,wall or ceiling. Intended for indoor use only.

FEATURES
• Adjustable second time delay
• Micro-based signal processing
• High sensitivity
• Available in white or brown enclosure

2. DIMENSIONS
Outdoor Request To Exit Motion Sensor With 0.5-64 Seconds Relay Hold Time
3. DESCRIPTION AND OPERATION
Outdoor Request To Exit Motion Sensor With 0.5-64 Seconds Relay Hold Time
4. DETECTION PATTERN

Outdoor Request To Exit Motion Sensor With 0.5-64 Seconds Relay Hold Time

5. INSTALLATION
Mounting Procedure
1. Select a mounting location over the center of the door or doors to be covered. The target must walk
directly toward the detector.Mount the detector on the ceiling,wall,or door frame.
2. Remove the front cover from the detector.
3. Route the wiring as necessary through the wiring entrance(refer to the item 3 description and oper- ation).For surface wiring,use the break out wiring entrance on the front cover(at the same end as the wire entrance).
4. Loosely mount the back cover to the mounting sur- face using the supplied mounting screws.
5. Aim the detector for the desired coverage.
6. Mount the front cover on the detector.
Long Range/Short Range Adjustment
The OD-22 can be set to detect individuals at either a long rang(several steps from the door) or at short range (immediately in front of the door).If the build- ing includes a lengthy approach to the exit doorway and no other foot traffic in the area, choose the long range setting.
Outdoor Request To Exit Motion Sensor With 0.5-64 Seconds Relay Hold Time
Setup and Testing
1. Apply power to the unit.
2. Wait at least 3 min for the detector to settle.
3. Test the unit by walking directly throgh the coverage area,to- ward the door.
4. Aim the detector up or down if necessary to obtain the proper coverage.
5. Check that the relay latch time is sufficient Adjust if necessary.
6. After confirming proper operation,replace the cover and walk test one more time to ensure the coverage has not changed.
6. WIRING
Latch Time
DIP Switch 1,2,and 3 set the relay time.Latch time is adjustable from 0.5 sec to 64 sec.It indicates the amount of time the relay can remain active after the detector first sees motion.
Table1: Latch Time DIP Switch Settings
Time(sec) Switch 1 Switch 2 Switch 3
0.5(Default) OFF OFF OFF
1 ON OFF OFF
2 OFF ON OFF
4 ON ON OFF
8 OFF OFF ON
16 ON OFF ON
32 OFF ON ON
64 ON ON ON
Table 2: LED Enable/Disable DIP Switch Settings
Switch 4 Function
OFF Disabled
ON Enabled (Default)
Table 3:Relay Mode DIP Switch Settings
Switch 5 Function
OFF Fail Secure
ON Fail safe(Default)
Table 4:Resettable/Non-resettable DIP Swithc Settings
Switch 6 Function
OFF Non-resettable
ON Resettable (Default)
7. TROUBLE SHOOTING AND MAINTENANCE
TROUBLE TROUBLE CAUSE REMEDY
Unit does not power up No or low imput power. Apply proper input voltage.
Input power polarity reversed. Correct wiring polarity.
Alarm LED does not light LED jumper is set to “LED OFF”. Set LED jumper to “LED ENABLE”
Incorrect sensor mounting height Increase / decrease mounting height
LED indicates light,no signal output Incorrect wiring at output terminals Correct wiring fault.
Lightning damage Replace sensor.
Unit continues to operate after the input power has been disconnected. The wire to the “V-” power input was discon- nected, the “V+” is still connected. Disconnect wire from the “V+” power input.

MAINTENANCE

INSPECTION: An inspection of this unit should be made periodically, consisting of ,but not limited to all mounting, wiring
and the condition of the interior area and components.
CLEANING : Clean the plastic parts of this unit with a soft, clean, cloth dampened with water.
TESTING : This unit should be tested rouinely for proper operation. At a minimum, operation should be fully checked yearly.

Send your message to this supplier
Send Now

Outdoor Request To Exit Motion Sensor With 0.5-64 Seconds Relay Hold Time

Ask Latest Price
Model Number :
OD-22
Place of Origin :
China
Brand Name :
ALEPH
Certification :
CE ISO
MOQ :
1pcs
Price :
Negotiable
Contact Supplier
Outdoor Request To Exit Motion Sensor With 0.5-64 Seconds Relay Hold Time

Ain Technology (Shenzhen) Co., Ltd

Active Member
6 Years
guangdong, shenzhen
Since 1935
Business Type :
Manufacturer, Importer, Exporter
Certification Level :
Active Member
Contact Supplier
Submit Requirement