(includes terminal-based linearity, hysteresis, and repeatability)
Measurement span | F | |
Reference accuracy | X ≤ span | ±0.055% of Span |
X > span | ±(0.005+0.02 URL/span)% of Span | |
X | 2 kPa (8 inH2O) | |
URL (upper range limit) |
5 kPa (20 inH2O) |
Measurement span | M | |
Reference accuracy | X ≤ span | ±0.055% of Span |
X > span | ±(0.005+0.0025 URL/span)% of Span | |
X | 5 kPa (20 inH2O) | |
URL (upper range limit) |
100 kPa (400 inH2O) |
Measurement span | H | |
Reference accuracy | X ≤ span | ±0.055% of Span |
X > span | ±(0.005+0.01 URL/span)% of Span | |
X | 100 kPa (400 inH2O) | |
URL (upper range limit) |
500 kPa (2000 inH2O) |
Measurement span | V | |
Reference accuracy | X ≤ span | ±0.055% of Span |
X > span | ±(0.005+0.005 URL/span)% of Span | |
X | 1.4 MPa (200 psi) | |
URL (upper range limit) |
14 MPa (2000 psi) |
EJA110E Specification Overview
Measurement Types | |
Primary Variable | Differential Pressure (DP) |
Secondary Variable | Static Pressure (SP) |
Reference Accuracy | |
Primary Variable | ±0.055% of Span |
Secondary Variable | ±0.5% of Span available |
Response Time | |
Primary Variable | 90 msec |
Secondary Variable | 360 msec |
Long Term Stability | |
Primary Variable | ±0.1% of URL per 10 years |
Over-pressure Effect | |
Primary Variable | ±0.03% of URL |
Rangeability | |
Primary Variable | 100:1 |
Related Part Number:
EJA120E-JES4G-912DB |
EJA120E-JES4J-812EB |
EJA120E-JES5G-934DJ/KU22/M01/D4/N4 |
EJA130E-JMS4G-712DD/D4 |
EJA130E-JMS5J-917DB/C1/X2 |
EJA130E-JHS4J-817EB/FF1/D4 |
EJA130E-JHS4J-817EB/FU1/D4 |
EJA130E-JMS5J-719DC/NS21/N4 |
EJA130E-EMS5B-99DA/X1/D4/M01/T09 |
EJA130E-JMS4G-91DDJ/KS21/X2/HC/N4 |
EJA130E-FHS5G-919DB/X2/D4/M01/T09/KS26 |
EJA130E-FMS5G-919DB/X2/D4/M01/T09/KS26 |
EJA130E-JMS5G-719DD/X2/D4/M01/T09/KU22 |
EJA130E-FMS5G-919DB/X2/D4/M01/T09/KS26 |
EJA130E-FMS5G-919DB/KS26/X2/D4/M01/T09 |
EJA210E-JMS4J-912DN-EJ14A2SE01-B |
EJA210E-JMS5J-912NN-WA13A1SW00-B/D4 |
EJA210E-DMS4J-912DN-EJ14A2SE01-B/D4 |
EJA210E-JHS4J-912DN-EA14A1SE01-B/D4 |