This isolated barrier is used for intrinsic safety applications.
General specifications |
||
---|---|---|
Signal type |
Digital Input |
|
Functional safety related parameters |
||
Safety Integrity Level (SIL) |
SIL 2 |
|
Systematic capability (SC) |
SC 3 |
|
Supply |
||
Connection |
Power Rail or terminals 14+, 15- |
|
Rated voltage |
19 ... 30 V DC |
|
Ripple |
≤ 10 % |
|
Rated current |
≤ 50 mA |
|
Power dissipation |
≤ 1 W |
|
Power consumption |
≤ 1 W |
|
Input |
||
Connection side |
field side |
|
Connection |
terminals 1+, 2+, 3-; 4+, 5+, 6- |
|
Rated values |
acc. to EN 60947-5-6 (NAMUR) |
|
Open circuit voltage/short-circuit current |
approx. 8 V DC / approx. 8 mA |
|
Switching point/switching hysteresis |
1.2 ... 2.1 mA / approx. 0.2 mA |
|
Line fault detection |
breakage I ≤ 0.1 mA , short-circuit I > 6 mA |
|
Pulse/Pause ratio |
min. 20 ms / min. 20 ms |
|
Output |
||
Connection side |
control side |
|
Connection |
output I: terminals 7, 8, 9 ; output II: terminals 10, 11, 12 |
|
Output I, II |
signal, relay |
|
Contact loading |
250 V AC/2 A/cos φ > 0.75; 126.5 V AC/4 A/cos φ > 0.75; 40 V DC/2 A resistive load |
|
Minimum switch current |
2 mA / 24 V DC |
|
Energized/De-energized delay |
approx. 20 ms / approx. 20 ms |
|
Mechanical life |
107 switching cycles |
|
Collective error message |
Power Rail |
|
Transfer characteristics |
||
Switching frequency |
≤ 10 Hz |
|
Galvanic isolation |
||
Input/Output |
reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
|
Input/power supply |
reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
|
Output/power supply |
reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
|
Output/Output |
reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
|
Indicators/settings |
||
Display elements |
LEDs |
|
Control elements |
DIP switch |
|
Configuration |
via DIP switches |
|
Labeling |
space for labeling at the front |
|
Directive conformity |
||
Electromagnetic compatibility |
|
|
|
Directive 2014/30/EU |
EN 61326-1:2013 (industrial locations) |
Low voltage |
|
|
|
Directive 2014/35/EU |
EN 61010-1:2010+A1:2019+A1:2019/AC:2019 |
Conformity |
||
Electromagnetic compatibility |
NE 21:2017 , EN 61326-3-1:2017 , EN IEC 61326-3-2:2018 |
|
Degree of protection |
IEC 60529:1989+A1:1999+A2:2013 |
|
Functional safety |
IEC/EN 61508:2010 |
|
Input |
EN 60947-5-6:2000 |
|
Ambient conditions |
||
Ambient temperature |
-40 ... 70 °C (-40 ... 158 °F) |
|
Mechanical specifications |
||
Degree of protection |
IP20 |
|
Connection |
screw terminals |
|
Mass |
approx. 150 g |
|
Dimensions |
20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2 |
|
|
Height |
119 mm |
|
Width |
20 mm |
|
Depth |
115 mm |
Mounting |
on 35 mm DIN mounting rail acc. to EN 60715:2001 |
|
Data for application in connection with hazardous areas |
||
EU-type examination certificate |
PTB 00 ATEX 2080 |
|
|
Marking |
|
|
Input |
Ex ia |
|
Voltage |
10.5 V |
|
Current |
13 mA |
|
Power |
34 mW (linear characteristic) |
Supply |
|
|
|
Maximum safe voltage |
253 V AC / 125 V DC (Attention! Um is no rated voltage.) |
Output |
|
|
|
Maximum safe voltage |
253 V AC (Attention! The rated voltage can be lower.) |
Fault indication output |
|
|
|
Maximum safe voltage |
40 V DC (Attention! Um is no rated voltage.) |
Certificate |
PF 08 CERT 0803 |
|
|
Marking |
|
Input |
Ex ic |
|
|
Voltage |
10.5 V |
|
Current |
13 mA |
|
Power |
34 mW (linear characteristic) |
Certificate |
TÜV 99 ATEX 1493 X |
|
|
Marking |
|
Galvanic isolation |
|
|
|
Input/Output |
safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
|
Input/power supply |
safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
Directive conformity |
|
|
|
Directive 2014/34/EU |
EN IEC 60079-0:2018+AC:2020 , EN 60079-7:2015+A1:2018 , EN 60079-11:2012 , EN IEC 60079-15:2019 |
International approvals |
||
FM approval |
|
|
|
FM certificate |
FM19US0207X |
|
Control drawing |
116-0035 |
UL approval |
E106378 |
|
|
Control drawing |
116-0473 (cULus) |
|
Contact loading |
250 V AC/2 A/cos φ > 0.75; 126.5 V AC/4 A/cos φ > 0.75; 30 V DC/2 A resistive load |
IECEx approval |
|
|
|
IECEx certificate |
IECEx PTB 11.0034 , IECEx TUN 19.0013X |
|
IECEx marking |
[Ex ia Ga] IIC |