2-channel isolated barrier, 230 V AC supply, Dry contact or NAMUR inputs, Relay contact output, Line fault detection (LFD), Reversible mode of operation, Up to SIL 2 acc. to IEC/EN 61508 / IEC/EN 61511, Housing width: 20 mm, Number of channels: 2-channel, Safety Integrity Level (SIL): SIL 2, Rated voltage: 207 ... 253 V AC, 45 ... 65 Hz, Field device: NAMUR sensor, Field device [2]: volt-free contact, Line fault detection, Type: 2 x relay (change-over contact), Reversible mode of operation
Technical Data
General specifications |
||
---|---|---|
Signal type |
Digital Input |
|
Functional safety related parameters |
||
Safety Integrity Level (SIL) |
SIL 2 |
|
Supply |
||
Connection |
terminals 14, 15 |
|
Rated voltage |
207 ... 253 V AC, 45 ... 65 Hz |
|
Power dissipation |
1.2 W |
|
Power consumption |
max. 1.3 W |
|
Input |
||
Connection side |
field side |
|
Connection |
terminals 1+, 2+, 3-; 4+, 5+, 6- |
|
Rated values |
acc. to EN 60947-5-6 (NAMUR) |
|
Open circuit voltage/short-circuit current |
approx. 8 V DC / approx. 8 mA |
|
Switching point/switching hysteresis |
1.2 ... 2.1 mA / approx. 0.2 mA |
|
Line fault detection |
breakage I ≤ 0.1 mA , short-circuit I > 6 mA |
|
Pulse/Pause ratio |
min. 20 ms / min. 20 ms |
|
Output |
||
Connection side |
control side |
|
Connection |
output I: terminals 7, 8, 9 ; output II: terminals 10, 11, 12 |
|
Output I, II |
signal ; relay |
|
Contact loading |
253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 40 V DC/2 A resistive load |
|
Energized/De-energized delay |
approx. 20 ms / approx. 20 ms |
|
Mechanical life |
107 switching cycles |
|
Transfer characteristics |
||
Switching frequency |
≤ 10 Hz |
|
Galvanic isolation |
||
Input/Output |
reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
|
Input/power supply |
reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
|
Output/power supply |
reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
|
Output/Output |
reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
|
Indicators/settings |
||
Display elements |
LEDs |
|
Labeling |
space for labeling at the front |
|
Directive conformity |
||
Electromagnetic compatibility |
|
|
|
Directive 2014/30/EU |
EN 61326-1:2013 (industrial locations) |
Low voltage |
|
|
|
Directive 2014/35/EU |
EN 61010-1:2010 |
Conformity |
||
Electromagnetic compatibility |
NE 21:2006 |
|
Degree of protection |
IEC 60529:2001 |
|
Input |
EN 60947-5-6:2000 |
|
Ambient conditions |
||
Ambient temperature |
-20 ... 60 °C (-4 ... 140 °F) |
|
Mechanical specifications |
||
Degree of protection |
IP20 |
|
Connection |
screw terminals |
|
Mass |
approx. 150 g |
|
Dimensions |
20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2 |
|
|
Height |
119 mm |
|
Width |
20 mm |
|
Depth |
115 mm |
Mounting |
on 35 mm DIN mounting rail acc. to EN 60715:2001 |
|
Data for application in connection with hazardous areas |
||
EU-type examination certificate |
PTB 00 ATEX 2081 |
|
|
Marking |
|
|
Input |
Ex ia |
|
Voltage |
10.6 V |
|
Current |
19.1 mA |
|
Power |
51 mW (linear characteristic) |
Supply |
|
|
|
Maximum safe voltage |
253 V AC (Attention! Um is no rated voltage.) |
Output |
|
|
|
Contact loading |
253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 40 V DC/2 A resistive load |
|
Maximum safe voltage |
253 V AC (Attention! The rated voltage can be lower.) |
Galvanic isolation |
|
|
|
Input/input |
not available |
|
Input/Output |
safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
|
Input/power supply |
safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
Directive conformity |
|
|
|
Directive 2014/34/EU |
EN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 |
International approvals |
||
FM approval |
|
|
|
Control drawing |
116-0035 |
UL approval |
|
|
|
Control drawing |
116-0145 |
CSA approval |
|
|
|
Control drawing |
116-0047 |
IECEx approval |
|
|
|
IECEx certificate |
IECEx PTB 11.0031 |
|
IECEx marking |
[Ex ia Ga] IIC |
Related Models:
KFU8-UFT |
KFD0-CS-Ex1.51P |
K-HM26-2M-261533 |
KFD0-CS-Ex2.50P |
NBB15-U1-E2 |
KFD0-CS-Ex2.51P |
NBB1,5-5GM25-E2 |
KFD0-RO-Ex2 |
NBB1,5-5GM25-E2-V3 |
KFD0-SCS-Ex1.55 |
NBB1,5-F79-E0 |
KFD0-SD2-Ex2.1045 |
NBB1,5-F79-E2 |
KFD0-SD2-Ex2.1245 |
NBB15-U1-Z2 |
KFD0-TR-Ex1 |
NBB5-18GM50-E2-V1 |
KFD0-CC-1 |
NBB15-30GM30-E2-V1 |
KFD0-HMS-16 |
NBB15-30GM50-A2-V1 |
KFD0-RSH-1.4S.PS2 |
NBB15-30GM50-E2 |
KFD0-SD2-EX1.10100 |
NBB15-30GM50-E2-M |
KFD0-SD2-EX1.1045 |
NBB15-30GM50-E2-V1 |
KFD2-UT2-1 |
NBB15-30GM50-E2-V1-M |
KFD2-CD-1.32 |
NBB8-18GM30-E2 |
KFD2-CD-EX1.32 |
NBB8-18GM30-E2-V1 |
KFD2-HMM-16 |
NBB8-18GM60-A2-V1 |
KFD2-SH-EX1.T |
NJ4-12GK-SN |
KFD2-UT2-1 |
NJ5-18GK-N |
KFD2-VR4-EX1.26 |
NJ5-18GK-N-150 |
KFU8-UFC-1.D |
NJ5-18GM-N |
V15-G-2M |
NJ8-18GK-N |
Z 787 |
RD0-FB-EX4 |
Z787.H |
RD0-TI-Ex8.FF.* |
HIC2031 |
Z787.F |
Z787.H.F |