ABB AI835A 3BSE051306R1 Thermocouple/mV Input Module
The AI835/AI835A provides 8 differential input channels for Thermocouple/mV measurements. Measurement ranges configurable per channel are: -30 mV to +75 mV linear, or TC Types B, C, E, J, K, N, R, S and T, for AI835A also D, L and U.
One of the channels (Channel 8) may be configured for “Cold Junction” (ambient) temperature measurements, thus serving as CJ-channel for Ch. 1...7. The junction temperature may be measured locally on the MTUs screw terminals, or on a connection unit distant form the device.
Alternatively, a fix junction temperature for the module may be set by the user (as parameter) or for AI835A also from the application. Channel 8 may be used in the same manner as Ch. 1...7 when no CJ-temperature measurement is needed.
General info
Article number | 3BSE051306R1 |
Type | Analog Input |
Signal specification | -30..75 mV linear; TC types B, C, D, E, J, K, L, N, R, S, T and U |
Number of channels | 8 |
Signal type | See table in S800 Modules and Termination Units, 3BSE020924 |
HART | No |
SOE | No |
Redundancy | No |
High integrity | No |
Intrinsic safety | No |
Mechanics | S800 |
Detailed data
Resolution | 15 bits |
Input impedance | > 1 MΩ |
Isolation | Groupwise isolated from ground |
Error | Max. 0.1% |
Temperature drift | Typ. 5 ppm/°C, Max. 7 ppm/°C |
Update cycle time | 280 + 80 * (number of active channels) ms at 50 Hz; 250 + 70 * (number of active channels) ms at 60 Hz |
Maximum field cable length | 600 meters (656 yards) |
CMRR, 50Hz, 60Hz | 120 dB |
NMRR, 50Hz, 60Hz | > 60 dB |
Rated insulation voltage | 50 V |
Dielectric test voltage | 500 V a.c. |
Power dissipation | 1.6 W |
Current consumption +5 V Modulebus | 75 mA |
Current consumption +24 V Modulebus | 50 mA |
Current consumption +24 V external | 0 |
Diagnostics
Front LED’s | F(ault), R(un), W(arning) |
Supervision | Module error´: reference channels, power supply low Channel error: open-circuit CJ-channel (ch 8): < -40 °C (-40°F) and > 100 °C (212°F) |
Status indication of supervision | Module Error, Module Warning, Channel error (8) |
Environment and certification
CE mark | Yes |
Electrical safety | EN 61010-1, UL 61010-1, EN 61010-2-201, UL 61010-2-201 |
Hazardous Location | C1 Div 2 cULus, C1 Zone 2 cULus, ATEX Zone 2 |
Marine certification | ABS, BV, DNV, LR |
Temperature, Operating | 0 to +55 °C (+32 to +131 °F), approvals are issued for +5 to +55 °C |
Temperature, Storage | -40 to +70 °C (-40 to +158 °F) |
Pollution degree | Degree 2, IEC 60664-1 |
Corrosion protection | ISA-S71.04: G3 |
Relative humidity | 5 to 95 %, non-condensing |
Max ambient temperature | 55 °C (131 °F), for vertical mounting in compact MTU 40 °C (104 °F) |
Protection class | IP20 according to IEC 60529 |
Mechanical operating conditions | IEC/EN 61131-2 |
EMC | EN 61000-6-4 and EN 61000-6-2 |
Overvoltage categories | IEC/EN 60664-1, EN 50178 |
Equipment class | Class I according to IEC 61140; (earth protected) |
RoHS compliance | DIRECTIVE/2011/65/EU (EN 50581:2012) |
WEEE compliance | DIRECTIVE/2012/19/EU |
Compatibility
Use with MTU | TU810, TU812, TU814, TU818, TU830, TU833 |
Keying code | BA |
Dimensions
Width | 45 mm (1.77”) |
Depth | 102 mm (4.01”), 111 mm (4.37”) including connector |
Height | 119 mm (4.7”) |
Weight | 0.22 kg (0.49 lbs.) |
Our brand:
【Honeywell】 Module DCS/PLC/Transmitter
【Emerson/Delta V】 Module/ CT Motor & Drives
【ABB】 I/O Module
【AB】 Module&Touch Screen
【Rosemount】 Transmitter
【Yokogawa】 Transmitter
【Yaskawa】 Servo Drive&Servo Motor
【GE/Fanuc】 IC69 Series PLC
【Mitsubishi】 Servo Drive&Servo Motor
(Modicon,SMC,SICK,NORGREN,Siemens,Ebmpapst etc.)
1, First, send us the brand, model code/pic of the nameplate, the quantity for inquiry. Then we will send the quote to you. after confirming the model and the quantity, then we will the PI to you.
2, You can transfer by Paypal/ Western Union/Trade assurance/ T/T. When we received the payment, then we will start to prepare the order for you asap.