ABB DI814 3BUR001454R1 DIGITAL INPUT 24V CURRENT 16 CH
The input voltage range is 18 to 30 volt dc and the input current source is 6 mA at 24 V. The inputs are divided into two individually isolated groups with eight channels and one voltage supervision input in each group. Every input channel consists of current limiting components, EMC protection components, input state indication LED and optical isolation barrier. The process voltage supervision input give channel error signals if the voltage disappears. The error signal can be read through the ModuleBus.
General info
Article number | 3BUR001454R1 |
Type | Digital Input |
Signal specification | 24 V d.c. |
Number of channels | 16 |
Signal type | Current sourcing |
HART | No |
SOE | No |
Redundancy | No |
High integrity | No |
Intrinsic safety | No |
Mechanics | S800 |
Detailed data
Input voltage range, "0" | -30 .. 5 V |
Input voltage range, "1" | 15 .. 30 V |
Input impedance | 3.5 kΩ |
Isolation | Groupwise isolated from ground, 2 groups with 8 channels |
Filter times (digital, selectable) | 2, 4, 8, 16 ms |
Current limiting | Sensor power can be current limited by the MTU |
Maximum field cable length | 600 meters (656 yards) |
Rated insulation voltage | 50 V |
Dielectric test voltage | 500 V a.c. |
Power dissipation | Typ. 1.8 W |
Current consumption +5 V Modulebus | 50 mA |
Current consumption +24 V Modulebus | 0 |
Current consumption +24 V external | 0 |
Diagnostics
Front LED’s | F(ault), R(un), W(arning), Channel 1-16 ("0" or "1") |
Supervision | Process voltage, 1 per group |
Status indication of supervision | Module Error, Module Warning, Channel error |
Environment and certification
CE mark | Yes |
Electrical safety | EN 61010-1, UL 61010-1, EN 61010-2-201, UL 61010-2-201 |
Hazardous Location | C1 Div 2 cULus, C1 Zone 2 cULus, ATEX Zone 2 |
Marine certification | ABS, BV, DNV, LR |
Temperature, Operating | 0 to +55 °C (+32 to +131 °F), approvals are issued for +5 to +55 °C |
Temperature, Storage | -40 to +70 °C (-40 to +158 °F) |
Pollution degree | Degree 2, IEC 60664-1 |
Corrosion protection | ISA-S71.04: G3 |
Relative humidity | 5 to 95 %, non-condensing |
Max ambient temperature | 55 °C (131 °F), for vertical mounting in compact MTU 40 °C (104 °F) |
Protection class | IP20 according to IEC 60529 |
Mechanical operating conditions | IEC/EN 61131-2 |
EMC | EN 61000-6-4 and EN 61000-6-2 |
Overvoltage categories | IEC/EN 60664-1, EN 50178 |
Equipment class | Class I according to IEC 61140; (earth protected) |
RoHS compliance | DIRECTIVE/2011/65/EU (EN 50581:2012) |
WEEE compliance | DIRECTIVE/2012/19/EU |
Compatibility
Use with MTU | TU810, TU812, TU814, TU830, TU838 |
Keying code | BE |
Dimensions
Width | 45 mm (1.77”) |
Depth | 102 mm (4.01”), 111 mm (4.37”) including connector |
Height | 119 mm (4.7”) |
Weight | 0.15 kg (0.33 lbs.) |
Our brand:
【Honeywell】 Module DCS/PLC/Transmitter
【Emerson/Delta V】 Module/ CT Motor & Drives
【ABB】 I/O Module
【AB】 Module&Touch Screen
【Rosemount】 Transmitter
【Yokogawa】 Transmitter
【Yaskawa】 Servo Drive&Servo Motor
【GE/Fanuc】 IC69 Series PLC
【Mitsubishi】 Servo Drive&Servo Motor
(Modicon,SMC,SICK,NORGREN,Siemens,Ebmpapst etc.)
1, First, send us the brand, model code/pic of the nameplate, the quantity for inquiry. Then we will send the quote to you. after confirming the model and the quantity, then we will the PI to you.
2, You can transfer by Paypal/ Western Union/Trade assurance/ T/T. When we received the payment, then we will start to prepare the order for you asap.