Emerson Power Supply Module Brand New Original Box KJ3225X1-BA1
Description:
KJ3225X1-BA1 RTD / Resistance Input Card
Power Specifications:
Local Bus Power 12 VDC at 160 mA
Environmental Specifications:
Ambient Temperature: -40°C to +70°C
Shock:10g ½ Sinewave for 11msec
Vibration 1mm Peak to Peak from 2 to 13.2Hz; 0.7g from 13.2 to 150Hz
Airborne Contaminants: ISA-S71.04 –1985 Airborne Contaminants Class G3
Relative Humidity: 5 to 95% Non-Condensing IP 20 Rating
Terminal Block key Position: C3
Note: Refer to the product label for serial number and location and date of manufacture.
Warning: This product has specific instructions for installation, removal and operation in hazardous areas.
Refer to document 12P2046 "DeltaV™ Scalable Process System Zone 2 Installation Instructions"
Other installation instructions are available in the "DeltaV™ M-Series Hardware Installation and Reference" manual.
Removal and Insertion: This unit cannot be removed or inserted with system power energized unless the area is known to be non‐hazardous and only one unit at a time may be removed or inserted.
For “nL” installation, an I/O loop assessment must be completed on all energy-limited nodes.A rotary keying system ensures compatibility between I/O cards and terminal blocks after installation is complete. The terminal block must have the keys set for the I/O card with which it is used.
Maintenance and Adjustment: This unit contains no user serviceable parts and
should not be disassembled for any reason.