Yokogawa Module for Compatible ST2 AAI835-H50/K4A00 4 to 20 mA 4-channel input
Product Description
More Information :
-
Manufacturer : Yokogawa
-
Product No. : AAI835-H50/K4A00
-
Product Type : Analog I/O Module (Current I/O)
-
AAI835 - Model : Analog I/O Module (4 to 20 mA, 4-channel input/4-channel output, Isolated channels)
-
H - Suffix Codes : With digital communication (HART protocol)
-
5 - Suffix Codes : With no explosion protection
-
0 - Suffix codes : Basic type
-
K4A00 - Option codes : With KS Cable Interface Adapter [Model: ATK4A-00]
-
Number of I/O channels : 4-channel input/4-channel output, isolated channels
-
I/O signal
- Input: 4 to 20 mA
- Output: 4 to 20 mA
-
Allowable input current : 25 mA
-
Withstanding voltage
- Between input/output and system: 500 V AC, for 1 minute
- Between input/output channels: 500 V AC, for 1 minute (*2)
-
Input resistance
- Power ON : 290 ? (at 20 mA) to 450 ? (at 4 mA) (*3)
- Power OFF : 500 k? or larger
-
Accuracy
- Input: ±16 µA
- Output: ±48 µA
-
Weight : 0.2 kg
-
Shipping Weight : 2 kg
LEGAL DISCLAIMER
Teknihaus is not an authorized dealer, agent or affiliate of any of the designers, brands, or manufacturers, the products of which are offered for sale on www.teknihaus.com. All trademarks, brand names, and logos mentioned are used for identification purposes only and are registered trademarks of their respective owners who reserve the rights of ownership. The use of trademark, brand name or product on our website is not intended to suggest that the company, trademark or brand is affiliated to or endorses our website. All products are 100% genuine and legally purchased from authorized sources.
The following explains the terminal blocks as well as the signal wiring that can be paired with the I/O Modules.
A pressure clamp terminal block is provided for the terminal connection with field devices. To expand terminals via terminal boards, connect a KS cable adapter to an I/O Module. When using a customer-furnished MIL connector cable, can directly connect to an I/O Module.
A dedicated terminal block is provided for a dual-redundant configuration
l Applicable Cables
Refer to the TI “CENTUM VP Installation Guidance” (TI 33J01J10-01EN), and use the proper cable appropriate for its
installation environment.
l Recommended Cable Thickness
Pressure clamp terminals
Without sleeve: 0.5 to 2 mm2
(AWG20 to 14)
With sleeve: 0.5 to 1.5 mm2
(AWG20 to 16)
M4 crimp terminals
0.5 to 2 mm2
(AWG20 to 14)
l Cable Termination Process when Pressure Clamp Terminals Are Used
ATA4S, ATD5S, ATI3S, ATB5S, ATF9S, A1BT4D, ATA4D, ATD5D, ATI3D, and ATB5D
Related Product
Our advantage Products: 【Honeywell】Module DCS / PLC 【Emerson / Delta V】Module 【ABB】Input Output Module 【AB】Module / Touch Screen 【Rosemount】Pressure and Temperature Transmitter 【Yokogawa】Pressure Transmitter 【Yaskawa】Servo Drive / Servo Motor 【GE/Fanuc】IC69 Series PLC 【Mitsubishi】Servo Drive / Servo Motor (Modicon,SMC,SICK,NORGREN,Siemens etc.) Company Introduction 