Specifications
Brand Name :
SHANCABLE
Model Number :
YJV,N2XY
Certification :
ISO,CE,IEC,TUV,KEMA
Place of Origin :
Shanghai, China
MOQ :
Negotiable
Price :
Negotiable
Payment Terms :
L/C, T/T
Supply Ability :
100KM/Week
Delivery Time :
10 Days
Packaging Details :
Wooden Drum
Rated Voltage :
12/20kV or 12.7/22kV
Conductor type :
Stranded Conductor (Class 2)
Core Mark :
Number or Color Strip
Sheath Mark :
ink Printing or Embossing
Drum Length :
500m or as per request
Outer Sheath Color :
Black or customized
Corporation :
shenghua group
Brand :
Sh Cable
Description

Professional Insulated XLPE Single Core Cable 12.7 / 22kV Rated Voltage N2XSY

Applications: XLPE Insulated Cable is used as power distribution and transmission line at rated voltage

12/20kV or 12.7/22kV

Construction:

Conductor Copper Conductor as per IEC 60228,Class 2
Circular or Shaped conductor
Insulation XLPE (Cross-Linked Polyethylene) rated at 90℃,many color optional
Metallic Screen optional Copper tape or copper wires braiding optional
Sheath PVC or FR-PVC type ST2 to IEC 60502, black or red or customization

Ordering Advice

Rated Voltage

Application Standard: IEC/BS/UL/GB

Number of Cores

Conductor Size & Construction

Type of Insulation

Armored or unarmored. If armor, the armor type & material

The Requirement of Sheath

Length of Cable & Packing Requirement

Other Requirement

Technical data: Rated voltage 12/20kV or 12.7/22kV

Maximum Conductor Temperature: under normal (90℃), emergency (130℃) or short circuit no more than 5 s (250℃) conditions.

Min. Ambient Temp. 0 OC, after installation and only when cable is in a fixed position

Min. Bending Radius: 20 x cable O.D for single core without armor

15 x cable O.D for multi core without armor

15 x cable O.D for single core with armor

12 x cable O.D for multi core with armor

Standards: International: IEC 60502, IEC 60228, (IEC 60332-3 for FR-type only)

China: GB/T 12706, (GB/T 18380-3 for FR-type only)

Other standards such as BS, DIN, VDE and ICEA upon request

Installation

1. The installation temperature should not over 20℃, If the ambient temperature is lower than 0℃, the cable should be preheated.
2. The bending radius of cable should not less than 8 times.

Technical parameter:

Nom. Cross-section of conductor Strands No./Dia. Of Conductor Insulation Thickness Sheath Thickness Approx. O.D. Approx. Weight Max. D.C Resistance of Conductor (20 ℃) Testing Voltage A.C Current Rating
mm2 pc/mm mm mm (mm) kg/km Ω /km kV/5min In air (A) In soil(A)
1 × 35 7/2.52 5.5 1.9 25 979 0.524 42 170 180
1 × 50 10/2.52 5.5 1.9 27 1155 0.387 42 205 215
1 × 70 14/2.52 5.5 2 28 1393 0.268 42 260 265
1 × 95 19/2.52 5.5 2 30 1681 0.193 42 315 315
1 × 120 24/2.52 5.5 2 32 1979 0.153 42 360 360
1 × 150 30/2.52 5.5 2.1 33 2301 0.124 42 410 405
1 × 185 37/2.52 5.5 2.2 35 2718 0.0991 42 470 455
1 × 240 48/2.52 5.5 2.2 37 3302 0.0754 42 555 530
1 × 300 61/2.52 5.5 2.3 39 3941 0.0601 42 640 595
1 × 400 61/2.97 5.5 2.4 43 4931 0.047 42 745 680
1 × 500 61/3.23 5.5 2.5 47 5956 0.0366 42 885 765
1 × 630 61/3.50 5.5 2.6 51 7769 0.0283 42 980 860
1 × 800 91/3.20 5.5 2.8 55 8945 0.0221 42 1100 950
1 × 1000 91/3.75 5.5 2.9 61 10918 0.0176 42 1230 1040
3 × 35 7/2.52 5.5 2.7 53 3348 0.524 42 140 155
3 × 50 10/2.52 5.5 2.9 55 3904 0.387 42 165 180
3 × 70 14/2.52 5.5 2.9 59 4623 0.268 42 210 220
3 × 95 19/2.52 5.5 3 62 5593 0.193 42 255 265
3 × 120 24/2.52 5.5 3.1 66 6495 0.153 42 290 300
3 × 150 30/2.52 5.5 3.2 69 7637 0.124 42 330 340
3 × 185 37/2.52 5.5 3.4 72 8803 0.0991 42 435 380
3 × 240 48/2.52 5.5 3.5 77 10729 0.0754 42 495 435
3 × 300 61/2.52 5.5 3.7 82 12723 0.0601 42 565 485
3 × 400 61/2.97 5.5 3.9 90 16207 0.047 42 640 520

Packing and shipping: We are capable of meeting the strictest delivery schedules according to per purchase order. Meeting the deadline is always the top priority as any delay in the delivery of cable can contribute to overall project delay and cost overrun.
Cable is supplied in wooden reels, corrugated boxes and coils. Cable ends are sealed with BOPP self-adhesive tape and non-hygroscopic sealing caps to protect the cable ends from moisture. The required marking shall be printed with a weather-proof material on the outsides of drum according to customer's requirement.

Professional Insulated XLPE Single Core Cable 12.7 / 22kV Rated Voltage N2XSY

Send your message to this supplier
Send Now

Professional Insulated XLPE Single Core Cable 12.7 / 22kV Rated Voltage N2XSY

Ask Latest Price
Brand Name :
SHANCABLE
Model Number :
YJV,N2XY
Certification :
ISO,CE,IEC,TUV,KEMA
Place of Origin :
Shanghai, China
MOQ :
Negotiable
Price :
Negotiable
Contact Supplier
Professional Insulated XLPE Single Core Cable 12.7 / 22kV Rated Voltage N2XSY
Professional Insulated XLPE Single Core Cable 12.7 / 22kV Rated Voltage N2XSY
Professional Insulated XLPE Single Core Cable 12.7 / 22kV Rated Voltage N2XSY
Professional Insulated XLPE Single Core Cable 12.7 / 22kV Rated Voltage N2XSY

Shanghai Shenghua Cable (Group) Co., Ltd.

Verified Supplier
9 Years
hunan, shanghai
Since 1997
Business Type :
Manufacturer
Total Annual :
150000000-200000000
Employee Number :
5000~6000
Certification Level :
Verified Supplier
Contact Supplier
Submit Requirement