With strong adaptability of power grid and load. Excellent ease of use. A DC branch can be divided into a maximum of two branches for fine battery management The 62.5KW small size and lightweight energy storage converter is suitable for both grid-connected and off-grid applications. It is easily for realizing parallel networking of multiple devices to form a small and medium-sized energy storage system. The DC side single stage voltage is 600 to 900V, and can be reach to 98.2% high efficiency. off grid available, strong load adaptability and our bidirectional converter is perfect for all types of load, which includes half wave load and impact load. Three level output, provide low harmonic and good power quality, 3U rack design, small size and easy to maintain.
Product specification
Model |
NESI-62.5KR1-1P |
NESI-62.5KR1-2P | |
DC side parameters | Voltage range | DC600V~DC900V | |
Rated power |
62.5kW | ||
Maximum current |
116A | ||
Number of DC channels | 1 | 2 | |
AC grid-connection parameters | Grid type |
3L+PE | |
Rated power |
62.5kW | ||
Rated voltage |
AC380V/400V | ||
Rated current |
95A | ||
Voltage range | -15%~+15% | ||
Rated frequency |
50Hz/60Hz | ||
Frequency range | Rated frequency±3Hz | ||
Power factor |
-1~+1 | ||
Output harmonic | ≤3% | ||
wiring |
3L+PE |
AC off-grid parameters | Rated power |
62.5kW |
Rated voltage |
AC380V | |
Rated frequency |
50Hz/60Hz | |
Rated current |
95A | |
Voltage accuracy |
1% | |
Frequency accuracy |
0.2Hz | |
Output harmonic | 3%@ linear full load | |
Dynamic response | 60ms@100% Linear load | |
Unbalanced load capacity |
100% | |
Overload capacity | Overload≤110%, run ≥10min; Overload [110%~120%], run ≥ 1min | |
Environment | Working temperature | -25℃~55℃(Derating when temperature is above 45 °C) |
Storage temperature | -40℃~70℃(No battery) | |
Relative humidity | 0%RH~95%RH,No condensation | |
Working altitude | When the temperature is 45 °C, derating is not required for 2000m. Derating ranges from 2000m to 4000m | |
Noise | <68dB | |
Communications and Management | Communication interface | RS485,CAN,LAN |
Communication protocol | CAN,ModBus TCP,ModBus RTU | |
Installation | Rack type | |
Highest efficiency |
98.2% | |
EMC |
Class A | |
Isolation method | No isolation | |
Protection grade |
IP20 | |
Cooling way | Air cooling, intelligent fan speed control | |
Size (W*H*D) |
435*135*650mm | |
Weight |
35kg |
All performance and parameters shall be subject to the latest confirmation of our technical department
.