1. Product description
1500 Series Intelligent Electro-pneumatic Valve Compact positioner positioner for integrated mounting on pneumatically operated process valves. Remote setpoint adjustment via a 4 - 20 mA signal. Simple installation through autotune function. The valve position indication is shown through LED components. As an option a 4-20mA feedback signal can be integrated.
2. Technical Data
Material | PC,PA6-GF30,SI |
Power supply | 24V DC ±10% |
Set-point signal | 4 - 20 mA |
Input resistance for set-point signal | 120Ω |
Ambient temperature | 0 - 70° |
Pneumatic connection | Plug-in hose connector G1/4 (internal Φ6mm) |
Electrical connection | M12 3-pins B-code (cable Φ 4-6mm); M12 4-pins D-code (cable Φ4-6mm) |
Supply pressure | 3-7 bar, specific values depending on the actuator |
Air flow rate | 17 L/min (Sup=0.6MPa); 58L/min (Sup=0.6MPa) |
Stroke control range | Linear 5-50mm; Rotary 90° |
Installation | As required, preferably with actuator in upright position, screw |
Protection class | IP66 |
Power consumption | <5W |
3. Product type selection
4. Features
5. Dimensions
6. Electrical connections and pneumatic connections
X2(Optional) | ||
---|---|---|
Pin | Description | Signal type |
1 | Analogue signal output + | 4 - 20mA |
3 | Analogue signal output GND | GND |
4 | NC | NULL |
X3 | ||
---|---|---|
Pin | Description | Signal type |
1 | Power supply + | +24 V |
2 | Power supply GND | GND |
3 | Set signal input + | 4 - 20 mA |
4 | Set signal input GND | GND |
P | Air supply enter (built-in filter, filter size 5 μm) |
R | Air exhaust |
C | Check valve |
A1 | Pilot air outlet 1 |
A2 | Pilot air outlet 2 |