1. Product description
Designed for integral pneumatic control valve, 1500 series intelligent electropn-peumatic valve positioner is suitable for angle seat valves and diaphragm valves particularly. With keypad, 1500 series is very easy to operate. By detecting the position sensor signal, 1500 positioner adjusts the valve position quickly and accurately.
2. Technical Data
Material | PC,PA6-GF30,SI |
Power supply | 24V DC ±10% |
Set-point signal | 4 - 20 mA |
Input resistance for set-point signal | 120Ω |
Ambient temperature | 0 - 70° |
Pneumatic connection | Plug-in hose connector G1/4 (internal Φ6mm) |
Electrical connection | M12 3-pins B-code (cable Φ 4-6mm); M12 4-pins D-code (cable Φ4-6mm) |
Supply pressure | 3-7 bar, specific values depending on the actuator |
Air flow rate | 17 L/min (Sup=0.6MPa); 58L/min (Sup=0.6MPa) |
Stroke control range | Linear 5-50mm; Rotary 90° |
Installation | As required, preferably with actuator in upright position, screw |
Protection class | IP66 |
Power consumption | <5W |
3. Product type selection
4. Structure
1 | Protective cover |
2 | Main body casing |
3 | Electrical connection |
4 | Pneumatic connection |
5 | Actuator connection |
5. Electrical connections and pneumatic connections
X2(Optional) | ||
---|---|---|
Pin | Description | Signal type |
1 | Analogue signal output + | 4 - 20mA |
3 | Analogue signal output GND | GND |
4 | NC | NULL |
X3 | ||
---|---|---|
Pin | Description | Signal type |
1 | Power supply + | +24 V |
2 | Power supply GND | GND |
3 | Set signal input + | 4 - 20 mA |
4 | Set signal input GND | GND |
P | Air supply enter (built-in filter, filter size 5 μm) |
R | Air exhaust |
C | Check valve |
A1 | Pilot air outlet 1 |
A2 | Pilot air outlet 2 |
6. Additional software functions