1. Product description
The angle seat control valve is combined with the intelligent positioner (1600) and the angle seat valve(2710). The valve spool design of the angle seat valve (2710) is different from the angle seat valve (2700). It’s flow characteristic is more suitable for the flow adjustment.
The product is easy to operate and has rich software functions. It can easily be operated via the LCD and keypad. It detects the external setting signal and the signal of internal displacement sensor, and adjusts valve stroke quickly and accurately by using automatic control algorithm and PWM control technology.
2. 2710 Angle Seat Valve Technical Datas
Valve Body Material | Stainless steel 304(CF8)/ 316(CF8M) |
Actuator Material | Plastic/ Stainless steel 304(CF8)/ 316(CF8M) |
Seal Material | PTFE/ PPL |
Working Pressure | 16Bar |
Available Size | DN15 - DN100 |
Working Temperature | -20 - 220℃ |
Available Connection | Thread, Clamp, Flanged, Welding |
Air Supply | 2.5 - 8Bar |
Standard | DIN, SMS, ISO, IDF, RJT, 3A, etc |
Certificate | CE |
3. 2710 Type Selection
4. Flow characteristic
Stroke(%) | Kv(%) | Stroke(%) | Kv(%) |
---|---|---|---|
0 | 0 | 55 | 56.3 |
5 | 5.1 | 60 | 64.8 |
10 | 6.3 | 65 | 74.9 |
15 | 6.6 | 70 | 82.7 |
20 | 7.2 | 75 | 84.3 |
25 | 7.9 | 80 | 89.1 |
30 | 10.9 | 85 | 93 |
35 | 17.8 | 90 | 97.3 |
40 | 26.7 | 95 | 97.9 |
45 | 35.2 | 100 | 100 |
50 | 45.1 |
5. Electrical connections and pneumatic connections
X1 | ||
---|---|---|
Pin | Description | Signal type |
1 | Analogue signal output + | 0/4 – 20 mA or 0 – 5/10 V |
2 | Binary signal output 1 | 0/24 V |
3 | Binary signal output 2 | 0/24 V |
4 | Binary signal input + | 0-3V =“0”, 15-30V =“1” |
5 | Signal common GND | GND |
X2(Optional for process control only) | ||
---|---|---|
Pin | Description | Signal type |
1 | Transmitter input + | +24 V |
2 | Transmitter signal output | 4 - 20mA |
3 | Transmitter GND | GND |
X3 | ||
---|---|---|
Pin | Description | Signal type |
1 | Power supply + | +24 V |
2 | Power supply GND | GND |
3 | Set signal input + | 0/4 – 20 mA or 0 – 5/10 V |
4 | Set signal input GND | GND |
P | Air supply enter (built-in filter, filter size 5 μm) |
R | Air exhaust |
C | Check valve |
A1 | Pilot air outlet 1 |
A2 | Pilot air outlet 2 |
6. Additional functions