1. Product description
The angle seat control valve is including the intelligent positioner (1600) and the angle seat valve(2710). Compared to the angle seat valve 2700, 2710 series flow characteristic is more suitable for the flow adjustment.
The product is easy to operate and with rich software functions. It can easily be operated via the LCD and keypad. It detects the external setting signal and the signal of internal displacement sensor, and adjusts valve stroke quickly and accurately by using automatic control algorithm and PWM control technology.
2. 2710 Angle Seat Valve Technical Datas
Valve Body Material | Stainless steel 304(CF8)/ 316(CF8M) |
Actuator Material | Plastic/ Stainless steel 304(CF8)/ 316(CF8M) |
Seal Material | PTFE/ PPL |
Working Pressure | 16Bar |
Available Size | DN15 - DN100 |
Working Temperature | -20 - 220℃ |
Available Connection | Thread, Clamp, Flanged, Weldind |
Air Supply | 2.5 - 8Bar |
Standard | DIN, SMS, ISO, IDF, RJT, 3A, etc |
Certificate | CE |
3. 2710 Type Selection
4. Dimension
Type | Actuator | D | R | G1 | H/LA | ||
---|---|---|---|---|---|---|---|
Screw thread | Welding ISO1127/4200 | Welding DIN11850 | |||||
DN10 | 40 | 50.5 | 27 | G1/8 | 259 | 260 | 260 |
50 | 62 | 34 | G1/8 | 271 | 272 | 272 | |
DN15 | 40 | 50.5 | 27 | G1/8 | 259 | 259 | 259 |
50 | 62 | 34 | G1/8 | 271 | 271 | 271 | |
DN20 | 50 | 62 | 34 | G1/8 | 275 | 275 | 275 |
DN25 | 50 | 62 | 34 | G1/8 | 281 | 281 | 281 |
63 | 77 | 41.5 | G1/8 | 303 | 303 | 303 | |
DN32 | 63 | 77 | 41.5 | G1/8 | 311 | 311 | 311 |
80 | 98 | 52 | G1/4 | 328 | 328 | 328 | |
DN40 | 63 | 77 | 41.5 | G1/8 | 319 | 319 | 319 |
80 | 98 | 52 | G1/4 | 335 | 335 | 335 | |
100 | 121 | 63 | G1/4 | 353 | 353 | 353 | |
DN50 | 63 | 77 | 41.5 | G1/8 | 330 | 330 | 330 |
80 | 98 | 52 | G1/4 | 345 | 345 | 345 | |
100 | 121 | 63 | G1/4 | 363 | 363 | 363 | |
DN65 | 80 | 98 | 52 | G1/4 | 370 | 370 | 370 |
100 | 121 | 63 | G1/4 | 387 | 387 | 387 |
5. Schematic diagram
6. Electrical connections and pneumatic connections
X1 | ||
---|---|---|
Pin | Description | Signal type |
1 | Analogue signal output + | 0/4 – 20 mA or 0 – 5/10 V |
2 | Binary signal output 1 | 0/24 V |
3 | Binary signal output 2 | 0/24 V |
4 | Binary signal input + | 0-3V =“0”, 15-30V =“1” |
5 | Signal common GND | GND |
X2(Optional for process control only) | ||
---|---|---|
Pin | Description | Signal type |
1 | Transmitter input + | +24 V |
2 | Transmitter signal output | 4 - 20mA |
3 | Transmitter GND | GND |
X3 | ||
---|---|---|
Pin | Description | Signal type |
1 | Power supply + | +24 V |
2 | Power supply GND | GND |
3 | Set signal input + | 0/4 – 20 mA or 0 – 5/10 V |
4 | Set signal input GND | GND |
P | Air supply enter (built-in filter, filter size 5 μm) |
R | Air exhaust |
C | Check valve |
A1 | Pilot air outlet 1 |
A2 | Pilot air outlet 2 |