Solar Inverter Pure Sine Wave Low Frequency Inverter Charger 4KW~6KW
Application Area
Feature
Parameter
Specification | ||||
Model: NB | 40248/96 | 50248/96 | 60248/96 | |
Rated Power | 4000W | 5000W | 6000W | |
Battery Voltage | 48V/96V | |||
Size(L*W*Hmm) | 460*245*445 | |||
Packing Size(L*W*Hmm) | 530*310*550 | |||
N.W.(kg) | 46 | 52 | 53 | |
G.W.(kg) | 48(Carton Packing) | 58(Wooden Packing) | 59(Wooden Packing) | |
Parameters | ||||
Input | Voltage Range | 73VAC~138VAC / 76VAC~144VAC / 79VAC~150VAC / 145VAC~275VAC / 152VAC~288VAC / 158VAC~300VAC | ||
Frequency Range | 45Hz~64Hz | |||
Output | Voltage Range | 110VAC±2% / 115VAC±2% / 120VAC±2% / 220VAC±2% / 230VAC±2% / 240VAC±2% (Battery Mode) | ||
Frequency Range | 50Hz±0.5 or 60Hz±0.5 | |||
Output Wave | Pure Sine Wave | |||
Total Harmonic Distortion | ≤3% | |||
Transfer Time | ≤4ms | |||
Efficiency | ≥85% | |||
Working Mode | Battery First/AC First/Saving Energy Mode | |||
AC Charging current | Max 15A | |||
Battery Type | According to Customer Requirements | |||
Display | LCD | |||
Thermal method | Cooling fan in intelligent control | |||
Communication | RS232(Optional) | |||
Protection | Over-load | Overload exceeds 110%,automatic shutdown in 30 secs;Overload exceeds 120%,automatic shutdown in 2 secs(Under mains supply mode, it will not shutdown if overload, just keeping sound) | ||
Short circuit | Output short-circuit, automatic shutdown after keeping sound 20 secs | |||
Battery | High or low voltage protection | |||
Reverse Polarity | Reverse Polarity protection(Optional) | |||
Environment | Noise | ≤55dB | ||
Temperature | -10℃~40℃ | |||
Humidity | 0%~95%(No condense) | |||
Alarm | A | Under normal working situation, buzzer without alarm sound | ||
B | When battery are fault or under overload protection, buzzer keeping sound 4 times each second | |||
C | When inverter starts in normal situation, buzzer reminds 5 times | |||
Note: All specifications are subject to charge without prior notice |