3 Phase High Frequency Online UPS , high frequency power supply
Key Features:
■ True double-conversion
■ DSP technology guarantees high performance
■ Output power factor 0.8
■ Wide input voltage range (110-300 VAC)
■ Active power factor correction in all phases
■ 50Hz/60Hz frequency converter mode
■ ECO mode operation for energy saving
■ Accepts dual-mains inputs
■ Emergency power off function (EPO)
■ Generator compatible
■ SNMP+USB+RS-232 multiple communications
■ 3-stage extendable charging design for optimized battery performance
■ Adjustable battery numbers
■ Maintenance bypass available
■ Optional N+X parallel redundancy
■ Optional isolation transformer offers full isolation and complete common mode noise rejection
Technical Specifications of Online UPS HP9335C Series:
MODEL | HP9335C 10-20KVA | ||||||
10K | 10K-XL | 15K | 15K-XL | 20K | 20K-XL | ||
PHASE | 3-phase in / 3-phase out | ||||||
CAPACITY | 10000 VA / 8000 W | 15000 VA / 12000 W | 20000 VA / 16000 W | ||||
INPUT | |||||||
NominalVoltage | 3 x 400 VAC (3Ph+N) | ||||||
InputVoltageRange | 305-478 VAC (3-phase) at 100% load ; 190-520 VAC (3-phase) at50% load | ||||||
Frequency Range | 46~54 Hz or 56~64Hz | ||||||
Power Factor | ≧ 0.99 @ 100% Load | ||||||
OUTPUT | |||||||
Output Voltage | 3 x 400V (3Ph+N) | ||||||
AC Voltage Regulation (Batt. Mode) | ± 1% | ||||||
Frequency Range(SynchronizedRange) | 46~54Hz or 56~64Hz | ||||||
46~54Hz or 56~64Hz | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz | ||||||
Harmonic Distortion | ≦ 2 % THD (Linear Load) ; ≦ 5 % THD (Non-linear Load) | ||||||
Transfer | AC Mode to Batt. Mode | Zero | |||||
Inverter to Bypass | Zero | ||||||
Waveform (Batt. Mode) | Pure Sinewave | ||||||
EFFICIENCY | |||||||
AC Mode | 89% | 89% | 89% | ||||
Battery Mode | 86% | 88% | 87% | ||||
BATTERY | |||||||
Standard Model | Battery Type | 12 V / 9 Ah | |||||
Numbers | 20 pcs (18 - 20 adjustable) | 20 pcs x 2 strings (18 - 20 adjustable) | |||||
Typical Recharge Time | 9 hours recover to 90% capacity | ||||||
Charging Current (max.) | 1A | 2A | 2A | ||||
Charging Voltage | 273 VDC ± 1% | ||||||
Long-run Model | Battery Type | Depending on the capacity of external batteries | |||||
Numbers | |||||||
Charging Current (max.) | 4A | 4A | 4A | ||||
Charging Voltage | 273 VDC ± 1% | ||||||
INDICATORS | |||||||
LCD Display | UPS status, Load level, Battery level, Input/Output voltage, Discharge timer,and Fault | ||||||
ALARM | |||||||
Battery Mode | Sounding every 4 seconds | ||||||
Low Battery | Sounding every second | ||||||
Overload | Sounding twice every second | ||||||
Fault | Continously sounding | ||||||
PHYSICAL | |||||||
Standard Model | Dimension,D x W xH(mm) | 815 x 250 x 826 | 815 x 250 x 826 | 815 x 250 x 826 | |||
Net Weight (kgs) | 109 | 164 | 164 | ||||
Long-run Model | Dimension,D x W xH(mm) | 592 x 250 x 826 | 592 x 250 x 826 | 592 x 250 x 826 | |||
Net Weight (kgs) | 38 | 40 | 40 | ||||
ENVIRONMENT | |||||||
Humidity | 0-95 % RH @ 0- 40°C (Non-condensing) | ||||||
Noise Leve | Less than 58dB @ 1 Meter | Less than 60dB @ 1 Meter | |||||
MANAGEMENT | |||||||
Smart RS-232 / USB | Supports Windows22000/2003/XP/Vista/2008, Windows27/8, Linux, Unix, and MAC | ||||||
Optional SNMP | Power management from SNMP manager and web browser |