Pump Performance Curve:
Fire Pumps shall meet the following basic requirements:
1. Each pump is to be tested hydrostatically for not less than 5 miniutes. The test pressure is to be not less
than 1.5 times the maximum working pressure of the pump, but in no case less than 250 psi (1724kpa)
2. A pump shall develop not less than 65 percent of the rated total head when discharging at 1.5 times rated
capacity. The maximum net pressure for a fire pump shall not exceed 140 percent of the rated head.
3. The maximum pump brake horsepower shall not exceed the HP rating its driver, including service factor.