1500KVA Natural Gas Generator Baudouin Engine
Power Definition and Operation Conditions for 1500KVA Natural Gas Generator Baudouin Engine
Type of Power | Operational Conditions |
Continuous Power COP |
1. Unlimited running time; 2. Operated with stable 100% load; 3. No overload capacity. |
Standby Power ESP |
1. Annual operation time shall be within 200 hours; 2. Running for more than 24 hours, average load shall not beyond 70%; 3. No overload capacity. |
Note: Engines are not allowed to run more than above requirements. |
Other Requirement for 1500KVA Natural Gas Generator Baudouin Engine
If natural gas is not as stipulated, there will be power loss for engine and life time of engine will be effected. Extra heat value won’t improve engine power. However, limited heat value will cause loss of engine power. If heat value is less than 28MJ/m³ and CH4 content is lower than 60%, the engines can’t work properly.
1500KVA Natural Gas Generator Baudouin Engine Technical Parameter & Specification
Engine Model | EB16V150 1280N6 |
Type | V type, 16 cylinders, electrical speed governing, each cylinder independent ignition, turbocharge and inter-cooling |
Number of Cylinder-Cylinder ID-Stroke Distance (mm) | 16-150×185 |
Displacement (L) | 52.3 |
Compression Ratio | 12.5 |
Sequence of Ignition | B3-B5-A3-A5-B2-A6-B1-B7-A1-A7-B4-B6-A4-B8-A2-A8 |
Mode of Starting | Electrical starting |
Rotation Direction | Anticlockwise (see from output end) |
(COP)/rpm( kW/r/min) | 1280kW/1800r/min |
Prime Power(PRP)/rpm( kW/r/min) | / |
Backup Power (ESP) /rpm( kW/r/min) | / |
Idling(r/min) | 700-750 |
Engine Control System | WOODWARD latest generation |
Ignition System | HOERBIGER smart ignition |
Turbocharger | ABB High Efficiency Turbocharger |
Speed Adjust Mode | Electrical |
Steady State Speed Regulation | ≤3% |
Natural Gas Consumption(MJ/kW·h) | 8.8 |
Net Weight of Engine (kg) | 5300 |
Engine Thermal Efficiency | Valid Thermal Efficiency≥41% (As per ISO3046 Standard) |
Notes: 1) Rated Power tolerance ±3%; 2) Rated operation condition natural gas consumption tolerance ±5%; 3) Rated operation condition rotation speed fluctuation ±0.5%.
|
Air Intake & Exhaust System, Cooling System
Air Filter | Intake Air Requirement (m3/h) | 6034 | Equipped |
Original Resistance | ≤3.5kPa | ||
Filtering Efficiency | ≥99% | ||
Inter-cooler | Structure Mode | Water-air Inter-cooler | Equipped |
Intercooling Low Temperature Water Radiation | Rated Cooling Power | 311kW | Optional |
Inlet/Outlet Water Temperature | 45℃/50℃ | ||
Low Temperature Water Pump | Equipped with Engine/ Mechanical Drive | ||
Jacket High Temperature Water Radiator | Inlet/Outlet Water Temperature | 80℃/90℃ | Optional |
Rated Cooling Power | 597kW | ||
Water Pump | Equipped with Engine/ Mechanical Drive | ||
Muffler | Exhaust Back Pressure | ≤5kPa | Equipped |
Muffler inlet/outlet Dimension | 2×DN250 | ||