Technical Specification of 1200kW Soundproof Natural Gas Generator
Genset | Type | Open Type ■ Canopy Type □ | |||
Model | EN1200NG-0.48kV | ||||
Country | Place | Indoor | |||
Continuous Power/Frequency | 1000kW/60Hz | Backup Power/Frequency | 1200kW/60Hz | ||
Electricity Efficiency % | 39.1% | Electricity Efficiency (MJ/kW·h) | 9.2 | ||
Dimensions (mm) |
5700*1950*2240 | Weight kg | 9150 | ||
Operation Mode | Single Unit□ Combined ■ Connect to Grid□ Emergency□ | ||||
Ambient |
1. Indoor■ Outdoor(Normal□ Sand□) 2. Ambient Temperature:-15℃-45℃ 3. Working Mode:Continuous■ Backup□ 4. Humidity ≤90% 5. Fuel Type: Natural Gas Methane Value MN≥80,Fuel Heat value ≥28MJ/Nm3 Note: If natural gas supply is different than above mentioned, kindly provide exact fuel composition to us. |
||||
Working Altitude | ≤1000m | ||||
Operation Noise | ≤118dB(A) | ||||
Grade of Performance (GB 2820) |
G2□ G3□ G4■ 1. 0-250kW sudden load test,genset frequency drop≤-10% and frequency resume to normal within 6.4S. 2. 400kW-0 sudden unload test, genset frequency increase ≤6.38% and frequency resume to normal within 8.3S. 3. At generator steady state (at continuous power with steady load, power factor≥0.8), rpm fluctuate range ≤±1.5%;
Above data acquired in laboratory with standard environment. Fuel shall be standard natural gas. |
||||
Alternator | Brand & Model | Stanford HCI634K | |||
Alternator Cover Standard Number | SAE0 | Disc Coupling Standard Number | 18 | ||
Rated Power | 1500KVA | Backup Power | / | ||
No. Of Bearings | Single Bearing■ Double Bearing□ | ||||
Alternator Parameter | Efficiency: 95.3% Power Factor: 0.8 | ||||
Parallel Control Cabinet | Brand/Model | DEIF AGC222+IOM220 | |||
Switches | ABB | ||||
Main Functions | Automatic synchronization, load distribution, auto-protection, data communication and recording etc. |
The engine rated power and rated fuel consumption rate is based on ISO3046-1 stipulated standard ambient conditions: ambient temperature 25℃, atmospheric pressure 100kPa and humidity 30%.
Power Definition and Operation Conditions for 1200kW Soundproof Natural Gas Generator
If natural gas is not as stipulated, there will be power loss for engine and life time of engine will be effected. Extra heat value won’t improve engine power. However, limited heat value will cause loss of engine power. If heat value is less than 28MJ/m³ and CH4 content is lower than 60%, the engines can’t work properly.