Mean Well Original Switch Power Supply SD-100C-12 DC conversion module 36-72VAC 12dc module 100W
Features :
MODEL | SD-100A-5 | SD-100B-5 | SD-100C-5 | SD-100D-5 | SD-100A-12 | SD-100B-12 | SD-100C-12 | SD-100D-12 | SD-100A-24 | SD-100B-24 | SD-100C-24 | SD-100D-24 | |
OUTPUT | DC VOLTAGE | 5V | 12V | 24V | |||||||||
RATED CURRENT | 18A | 20A | 8.5A | 4.2A | |||||||||
CURRENT RANGE | 0 ~ 18A | 0 ~ 20A | 0 ~ 8.5A | 0 ~ 4.2A | |||||||||
RATED POWER | 90W | 100W | 102W | 100.8W | |||||||||
RIPPLE & NOISE (max.) Note.2 | 100mVp-p | 120mVp-p | 150mVp-p | ||||||||||
VOLTAGE ADJ. RANGE | 4.5 ~ 5.5VDC | 11 ~ 16VDC | 23 ~ 30VDC | ||||||||||
VOLTAGE TOLERANCE Note.3 | ±2.0% | ±1.0% | ±1.0% | ||||||||||
LINE REGULATION | ±0.5% | ±0.3% | ±0.2% | ||||||||||
LOAD REGULATION | ±0.5% | ±0.3% | ±0.2% | ||||||||||
SETUP, RISE TIME | 2s, 50ms(only D mode) at full load | ||||||||||||
HOLD UP TIME (Typ.) | 20ms(only D mode) at full load | ||||||||||||
INPUT | VOLTAGE RANGE | A:9.5 ~ 18VDC B:19 ~ 36VDC C:36 ~ 72VDC D:72 ~ 144VDC or 85 ~ 132VAC | |||||||||||
EFFICIENCY (Typ.) | 78% | 74% | 75% | 76% | 82% | 75% | 77% | 80% | 84% | 78% | 81% | 83% | |
DC CURRENT (Typ.) | 9.7A/12V | 4.8A/24V | 2.4A/48V | 1.8A/96V | 10.4A/12V | 4.8A/24V | 2.4A/48V | 1.8A/96V | 10A/12V | 4.8A/24V | 2.4A/48V | 1.8A/96V | |
INRUSH CURRENT (Typ.) | D:18A/96VDC | ||||||||||||
LEAKAGE CURRENT | <0.75mA/120VAC(SD-100D) | ||||||||||||
PROTECTION | OVERLOAD | 105 ~ 135% rated output power | |||||||||||
Protection type : Hiccup mode, recovers automatically after fault condition is removed | |||||||||||||
OVER VOLTAGE | 5.75 ~ 6.75V/10% load | 16.8 ~ 20V/10% load | 31.5 ~ 37.5V 5% load | 31.5 ~ 37.5V/10% load | |||||||||
Protection type : Hiccup mode, recovers automatically after fault condition is removed | |||||||||||||
ENVIRONMENT | WORKING TEMP. | -15 ~ +60℃(SD-100A), -10 ~ +60℃(SD-100B/C/D) (Refer to "Derating Curve") | |||||||||||
WORKING HUMIDITY | 20 ~ 90% RH non-condensing | ||||||||||||
STORAGE TEMP., HUMIDITY | -20 ~ +85℃, 10 ~ 95% RH non-condensing | ||||||||||||
TEMP. COEFFICIENT | ±0.03%/℃ (0 ~ 50℃) | ||||||||||||
VIBRATION | 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes | ||||||||||||
SAFETY & EMC (Note 4) | SAFETY STANDARDS | IEC/BS EN/EN 62368-1(for D type only), EAC TP TC 004 approved, design refer to AS/NZS 62368.1 | |||||||||||
WITHSTAND VOLTAGE | I/P-O/P:1.5KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC | ||||||||||||
ISOLATION RESISTANCE | I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH | ||||||||||||
EMC EMISSION | Compliance to BS EN/EN55032 (CISPR32) Class B, EAC TP TC 020 | ||||||||||||
EMC IMMUNITY | Compliance to BS EN/EN61000-4-2,3,4,6,8, light industry level, EAC TP TC 020 | ||||||||||||
OTHERS | MTBF | 2600.2K hrs min. Telcordia SR-332 (Bellcore) ; 399.9K hrs min. MIL-HDBK-217F (25℃) | |||||||||||
DIMENSION | 199*98*38mm (L*W*H) | ||||||||||||
PACKING | 0.65Kg; 20pcs/13.8Kg/0.85CUFT | ||||||||||||
NOTE | 1. All parameters NOT specially mentioned are measured at 12,24,48,96VDC input, rated load and 25℃ of ambient temperature. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. 3. Tolerance : includes set up tolerance, line regulation and load regulation. 4. The power supply is considered a component which will be installed into a final equipment. |
Solutions
We provide a complete solutions including site survey, propose professional plan according to customer’s request ,technical support, and maintenance service for Telecommunication Companies in and out of China. We have a competent team and a network of trusted Partners around the world.
FAQ :
1. How do you control the quality?
A:All products before the shipment are simulated usage scenarios, load and full load and current sharing test to ensure the quality of the product.
2. What is your minimum order quantity?
A:There is no minimum order quantity, and one can also be done. The only difference is the price and schedule.
3. Can you introduce your company?
A:I am very honored. I will send you the company’s introduction document later to give you a more comprehensive and direct introduction to our company’s information.
4. What are the advantages of your company?
A:Adequate inventory, and supply guarantee for the subsequent renewal of supply, flexible provided according to different to different needs of customers, providing different solutions.
5. Can i send samples?Report it to me along with the price?
A:You can send samples, the samples are subject to large pride, and the freight needs to be borne by you.
6. How do your company deal with the problem on quality?
A:Our company has been doing this industry for almost 10 years. It has already had a certain reputation. We will carefully analyze it. If it is indeed our quality problem, you can rest assured that it will do things according to the contract agreement and will never let you have any after the worries, our service team will be happy to serve you.
7 What about the quality ?
A:100% original with new package. we will test each item before posted to make sure each item with good quality.
8 How many months for guarantee ?
A: 1 year quality guarantee
9 How to deal with any inferior -quality goods ?