Mean Well DPR Series 3200W DPR-3200-24 DPR-3200-48 DHP-1UT DBR-3200
Wattage :
3200
Features :
Complete rack mountable front end solution: rectifier and charger
1U low profile
19 inch rack shelf available
Technical
MODEL | DRP-3200-24 | DRP-3200-48 | |||
OUTPUT | DC VOLTAGE | 24V | 48V | ||
RATED CURRENT | 133A | 67A | |||
CURRENT RANGE | 0 ~ 133A | 0 ~ 67A | |||
RATED POWER | 3192W | 3216W | |||
RIPPLE & NOISE (max.) Note.2,3 | 300mVp-p | 480mVp-p | |||
VOLTAGE ADJ. RANGE | 23.5 ~ 30V | 47.5 ~ 58.8V | |||
VOLTAGE TOLERANCE Note.4 | ±1.0% | ±1.0% | |||
LINE REGULATION | ±0.5% | ±0.5% | |||
LOAD REGULATION | ±0.5% | ±0.5% | |||
SETUP, RISE TIME | 1500ms, 60ms/230VAC at full load | ||||
HOLD UP TIME (Typ.) | 16ms / 230VAC at 75% load 9ms / 230VAC at full load | ||||
INPUT | VOLTAGE RANGE Note.5 | 90 ~ 264VAC 127 ~ 370VDC | |||
FREQUENCY RANGE | 47 ~ 63Hz | ||||
POWER FACTOR (Typ.) | 0.97/230VAC at full load | ||||
EFFICIENCY (Typ.) Note.6 | 93.5% | 94.5% | |||
AC CURRENT (Typ.) Note.5 | 17A/230VAC | ||||
INRUSH CURRENT (Typ.) | COLD START 55A/230VAC | ||||
LEAKAGE CURRENT | <1.5mA / 230VAC | ||||
PROTECTION |
OVERLOAD | 105 ~ 115% rated current | |||
Protection type : Constant current limiting, shut down O/P voltage after 5 sec. After O/P voltage falls, re-power on to recover | |||||
OVER VOLTAGE | 31.5 ~ 37.5V | 63 ~ 75V | |||
Protection type : Shut down o/p voltage, re-power on to recover | |||||
OVER TEMPERATURE | Shut down o/p voltage, recovers automatically after temperature goes down | ||||
FUNCTION |
OUTPUT VOLTAGE PROGRAMMABLE(PV) | Adjustment of output voltage is allowable to 50 ~ 125% of nominal output voltage Please refer to the Function Manual in following pages | |||
CONSTANT CURRENT LEVEL PROGRAMMABLE(PC) | Adjustment of constant current level is allowable to 20 ~ 100% of rated current. Please refer to the Function Manual in following pages | ||||
REMOTE ON-OFF CONTROL | By electrical signal or dry contact Power ON:short Power OFF:open. Please refer to the Function Manual in following pages | ||||
REMOTE SENSE | Compensate voltage drop on the load wiring up to 0.5V. Please refer to the Function Manual in following pages | ||||
AUXILIARY POWER | 5V @ 0.3A, tolerance ±10%, ripple 150mVp-p, 12V @ 0.8A, tolerance ±10%, ripple 450mVp-p | ||||
ALARM SIGNAL | Isolated TTL signal output for T-Alarm, AC-OK and DC-OK. Please refer to the Function Manual in following pages | ||||
ENVIRONMENT | WORKING TEMP. | -30 ~ +70℃ (Refer to "Derating Curve") | |||
WORKING HUMIDITY | 20 ~ 90% RH non-condensing | ||||
STORAGE TEMP., HUMIDITY | -40 ~ +85℃, 10 ~ 95% RH non-condensing | ||||
TEMP. COEFFICIENT | ±0.03%/℃ (0 ~ 50℃) | ||||
VIBRATION | 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes | ||||
SAFETY & EMC (Note 9) | SAFETY STANDARDS | UL62368-1, CSA C22.2 No. 62368-1, TUV BS EN/EN62368-1, EAC TP TC 004 approved | |||
WITHSTAND VOLTAGE | I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:1.5KVAC | ||||
ISOLATION RESISTANCE | I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH | ||||
EMC EMISSION | Parameter | Standard | Test Level / Note | ||
Conducted | BS EN/EN55032 (CISPR32) | Class B | |||
Radiated | BS EN/EN55032 (CISPR32) | Class A | |||
Harmonic Current | BS EN/EN61000-3-2 | ----- | |||
Voltage Flicker | BS EN/EN61000-3-3 | ----- | |||
EMC IMMUNITY | BS EN/EN55024, BS EN/EN61000-6-2 | ||||
Parameter | Standard | Test Level / Note | |||
ESD | BS EN/EN61000-4-2 | Level 3, 8KV air ; Level 2, 4KV contact | |||
Radiated | BS EN/EN61000-4-3 | Level 3 | |||
EFT / Burst | BS EN/EN61000-4-4 | Level 3 | |||
Surge | BS EN/EN61000-6-2 | 2KV/Line-Line 4KV/Line-Earth | |||
Conducted | BS EN/EN61000-4-6 | Level 3 | |||
Magnetic Field | BS EN/EN61000-4-8 | Level 4 | |||
Voltage Dips and Interruptions | BS EN/EN61000-4-11 | >95% dip 0.5 periods, 30% dip 25 periods, >95% interruptions 250 periods | |||
OTHERS | MTBF | 535.5K hrs min. Telcordia SR-332 (Bellcore) ; 44.6K hrs min. MIL-HDBK-217F (25℃) | |||
DIMENSION | 325*107*41mm (L*W*H) | ||||
PACKING | 2.65Kg;4pcs/11.6Kg/0.87CUFT | ||||
NOTE | 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. 3. Under variable load application or parallel operation ripple of the output voltage may be higher than the SPEC at light load condition. It will go back to normal ripple level once the output load is more than 5%. 4. Tolerance : includes set up tolerance, line regulation and load regulation. 5. Derating may be needed under low input voltages. Please check the derating curve for more details. 6. The efficiency is measured at 75% load. 7. If use PV signal to adjust Vo, under certain operating conditions, ripple noise of Vo might slightly go over rating defined in this specification. 8. Output will shut down after O/P voltage is below < 80% of Vset for 5 sec, re-power on to recover. 9. The power supply is considered a component which will be installed into a final equipment. All the EMC tests are been executed by mounting the unit on a 600mm*900mm metal plate with 1mm of thickness. The final equipment must be re-confirmed that it still meets EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.” (as available on http://www.meanwell.com) 10. The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft}. ※ Product Liability Disclaimer:For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx |
Solutions
We provide a complete solutions including site survey, propose professional plan according to customer’s request ,technical support, and maintenance service for Telecommunication Companies in and out of China. We have a competent team and a network of trusted Partners around the world.
FAQ :
1. How do you control the quality?
A:All products before the shipment are simulated usage scenarios, load and full load and current sharing test to ensure the quality of the product.
2. What is your minimum order quantity?
A:There is no minimum order quantity, and one can also be done. The only difference is the price and schedule.
3. Can you introduce your company?
A:I am very honored. I will send you the company’s introduction document later to give you a more comprehensive and direct introduction to our company’s information.
4. What are the advantages of your company?
A:Adequate inventory, and supply guarantee for the subsequent renewal of supply, flexible provided according to different to different needs of customers, providing different solutions.
5. Can i send samples?Report it to me along with the price?
A:You can send samples, the samples are subject to large pride, and the freight needs to be borne by you.
6. How do your company deal with the problem on quality?
A:Our company has been doing this industry for almost 10 years. It has already had a certain reputation. We will carefully analyze it. If it is indeed our quality problem, you can rest assured that it will do things according to the contract agreement and will never let you have any after the worries, our service team will be happy to serve you.
7 What about the quality ?
A:100% original with new package. we will test each item before posted to make sure each item with good quality.
8 How many months for guarantee ?
A: 1 year quality guarantee
9 How to deal with any inferior -quality goods ?
A: Goods can be post by with our charge of post fee for any bad quality products within guarantee time.