Mean Well HDR series HDR-15 HDR-30 HDR-60 HDR-100
Mean Well Portable Type Metal Enclosure Charger NPB-120-12 NPB-120-24 NPB-120-48
Model
New models:
NPB-120 / NPB-240 / NPB-360
Old models:
PA-120 / PB-120
Standard type highly reliable wide voltage range charger
Metal enclosure for better heat dissipation , leading lower touch temperature
Easy and flexible adjustment:
‧ Charging voltage adjustable through front panel (10.5~15.2V, 21~30.4V, 42~60.8V)
‧ Charging current adjustable through panel (50~100% of rated current)
‧ 2 or 3 stage selectable by DIP S.W. on front panel
Protections: Short circuit, over voltage, over temperature, battery reverse polarity
Comply with UL/EN62368-1 and IEC60335-1/2-29 dual certifications
Multiple DC output plugs selectable: Anderson, terminal block and 4 pin power pin
Technical
MODEL | HDR-15-5 | HDR-15-12 | HDR-15-15 | HDR-15-24 | HDR-15-48 | |||
OUTPUT | DC VOLTAGE | 5V | 12V | 15V | 24V | 48V | ||
RATED CURRENT | 2.4A | 1.25A | 1A | 0.63A | 0.32A | |||
CURRENT RANGE | 0 ~ 2.4A | 0 ~ 1.25A | 0 ~ 1A | 0 ~ 0.63A | 0 ~ 0.32A | |||
RATED POWER | 12W | 15W | 15W | 15.2W | 15.4W | |||
RIPPLE & NOISE (max.) Note.2 | 80mVp-p | 120mVp-p | 120mVp-p | 150mVp-p | 240mVp-p | |||
VOLTAGE ADJ. RANGE | 4.5 ~ 5.5V | 10.8 ~ 13.8V | 13.5 ~ 18V | 21.6 ~ 29V | 43.2 ~ 55.2V | |||
VOLTAGE TOLERANCE Note.3 | ±2.0% | ±1.0% | ±1.0% | ±1.0% | ±1.0% | |||
LINE REGULATION | ±1.0% | ±1.0% | ±1.0% | ±1.0% | ±1.0% | |||
LOAD REGULATION | ±1.0% | ±1.0% | ±1.0% | ±1.0% | ±1.0% | |||
SETUP, RISE TIME | 2000ms, 80ms/230VAC 2000ms, 80ms/115VAC at full load | |||||||
HOLD UP TIME (Typ.) | 30ms/230VAC 12ms/115VAC at full load | |||||||
INPUT | VOLTAGE RANGE | 85 ~ 264VAC (277VAC operational ) 120 ~ 370VDC (390VDC operational ) | ||||||
FREQUENCY RANGE | 47 ~ 63Hz | |||||||
EFFICIENCY (Typ.) | 80% | 85% | 85.5% | 86% | 87% | |||
AC CURRENT (Typ.) | 0.5A/115VAC 0.25A/230VAC | |||||||
INRUSH CURRENT (Typ.) | COLD START 25A/115VAC 45A/230VAC | |||||||
PROTECTION |
OVERLOAD | 110 ~ 145% rated output power | ||||||
Hiccup mode when output voltage <50%, recovers automatically after fault condition is removed Constant current limiting within 50% ~100% rated output voltage, recovers automatically after fault condition is removed | ||||||||
OVER VOLTAGE | 5.75 ~ 6.75V | 14.2 ~ 16.2V | 18.8 ~ 22.5V | 30 ~ 36V | 56.5 ~ 64.8V | |||
Protection type : Shut off o/p voltage, clamping by zener diode | ||||||||
ENVIRONMENT | WORKING TEMP. | -30 ~ +70℃ (Refer to "Derating Curve") | ||||||
WORKING HUMIDITY | 20 ~ 90% RH non-condensing | |||||||
STORAGE TEMP., HUMIDITY | -40 ~ +85℃, 10 ~ 95% RH non-condensing | |||||||
TEMP. COEFFICIENT | ±0.03%/℃ (0 ~ 50℃) RH non-condensing | |||||||
VIBRATION | 10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6 | |||||||
OPERATING ALTITUDE | 2000 meters | |||||||
OVER VOLTAGE CATEGORY | Ⅲ; According to EN61558, EN50178,EN60664-1, EN62477-1; altitude up to 2000 meters | |||||||
SAFETY & EMC (Note 4) | SAFETY STANDARDS | UL62368-1, UL508, TUV BS EN/EN61558-2-16, BS EN/EN61558-1, IEC62368-1, EAC TP TC 004, BSMI CNS14336-1 approved; Design refer to TUV BS EN/EN62368-1 | ||||||
WITHSTAND VOLTAGE | I/P-O/P:4KVAC | |||||||
ISOLATION RESISTANCE | I/P-O/P:100M Ohms / 500VDC / 25℃/ 70% RH | |||||||
EMC EMISSION | Parameter | Standard | Test Level / Note | |||||
Conducted | BS EN/EN55032(CISPR32), CNS13438 | Class B | ||||||
Radiated | BS EN/EN55032(CISPR32), CNS13438 | Class B | ||||||
Harmonic Current | BS EN/EN61000-3-2 | Class A | ||||||
Voltage Flicker | BS EN/EN61000-3-3 | ------- | ||||||
EMC IMMUNITY | BS EN/EN55024, BS EN/EN55035, BS EN/EN61000-6-2, BS EN/EN61204-3 | |||||||
Parameter | Standard | Test Level /Note | ||||||
ESD | BS EN/EN61000-4-2 | Level 3, 8KV air; Level 2, 4KV contact, criteria A | ||||||
Radiated Susceptibility | BS EN/EN61000-4-3 | Level 3, criteria A | ||||||
EFT/Burest | BS EN/EN61000-4-4 | Level 3, criteria A | ||||||
Surge | BS EN/EN61000-4-5 | Level 4,2KV/L-N, criteria A | ||||||
Conducted | BS EN/EN61000-4-6 | Level 3, criteria A | ||||||
Magnetic Field | BS EN/EN61000-4-8 | Level 4, criteria A | ||||||
Voltage Dips and interruptions | BS EN/EN61000-4-11 | >95% dip 0.5 periods, 30% dip 25 periods, >95% interruptions 250 periods | ||||||
OTHERS | MTBF | 3724.3K hrs min. Telcordia SR-332 (Bellcore) ; 1166.1K hrs min. MIL-HDBK-217F (25℃) | ||||||
DIMENSION | 17.5*90*54.5mm (W*H*D) | |||||||
PACKING | 78g;160pcs/13.5Kg/1.14CUFT |
Solutions
We provide a complete solutions including site survey, propose professional plan according to customer’s request ,technical support, and maintenance service for Telecommunication Companies in and out of China. We have a competent team and a network of trusted Partners around the world.
FAQ :
1. How do you control the quality?
A:All products before the shipment are simulated usage scenarios, load and full load and current sharing test to ensure the quality of the product.
2. What is your minimum order quantity?
A:There is no minimum order quantity, and one can also be done. The only difference is the price and schedule.
3. Can you introduce your company?
A:I am very honored. I will send you the company’s introduction document later to give you a more comprehensive and direct introduction to our company’s information.
4. What are the advantages of your company?
A:Adequate inventory, and supply guarantee for the subsequent renewal of supply, flexible provided according to different to different needs of customers, providing different solutions.
5. Can i send samples?Report it to me along with the price?
A:You can send samples, the samples are subject to large pride, and the freight needs to be borne by you.
6. How do your company deal with the problem on quality?
A:Our company has been doing this industry for almost 10 years. It has already had a certain reputation. We will carefully analyze it. If it is indeed our quality problem, you can rest assured that it will do things according to the contract agreement and will never let you have any after the worries, our service team will be happy to serve you.
7 What about the quality ?
A:100% original with new package. we will test each item before posted to make sure each item with good quality.
8 How many months for guarantee ?
A: 1 year quality guarantee
9 How to deal with any inferior -quality goods ?
A: Goods can be post by with our charge of post fee for any bad quality products within guarantee time.