Modbus Protocol Interface
Engineering Bootloader Mode
Monitoring Event Log
Direct Alarm Message
EPO mode (Emergency Power Off)
Hot swappable module with LED indicator
Standard 19” 2U rack mount
Zero transfer time
DC Mode / AC Mode selectable (Dual input AC / DC)
High efficiency up to 95% at AC Mode
Up to 32 modules can be connected in parallel (up to 51.2KW)
CE / FCC approved
MODEL | SR-1600-124 PLUS, SR-1600-148 PLUS, SR-1600-224 PLUS, SR-1600-248 PLUS |
Main Features | ◎ New Intelligent Power Conversion Control~ (Software) ◎ Module design hot-swappable, redundancy rack mount inverter ◎ Parallelable module up to 32 pcs ◎ Selectable DC Mode / AC Mode / AC Sharing |
AC Output Voltage | 100~120VAC; 200~240VAC |
Rated Power | 1200W/1600VA; 1600W/1600VA; 1200W/1600VA; 1600W/1600VA |
Surge Power | ─ |
Output Waveform | Pure Sine Wave |
Frequency | 50/60 Hz |
DC Output Voltage | ─ |
DC Output Voltage Range | ─ |
DC Input Voltage | 24V / 48V |
DC Input Voltage Range | 18~34VDC ± 3%; 36~68VDC ± 3%; 18~34VDC ± 3%; 36~68VDC ± 3% |
Efficiency | AC Mode: 95% DC Mode: 89%; 90%; 90%; 91% |
Operating Temperature | -25°C ~ 40°C ; Power De-rating from 40°C to 60°C |
Storage Temperature | -40~70℃ |
Safety | CE / FCC |
Dimension (WxHxD) | Module: 105x83x410 mm; Shelf: 446x85x509 mm |
Weight (Net) | Module: 3.8kg; Shelf: 6.5kg |
Socket Type | Terninal |