RS1200 Six Phase Secondary Injection Microcomputer Protective Relay Tester With 1 Year Warranty
Wuhan Rising Electric.,CO is specialized in manufacturing all grades of transformer testing equipment, load no-load transformer characteristic tester, automatic ratio groups of test instrument, transformer winding deformation tester, power frequency testing transformer, automatic anti jamming tester, series resonance test device, partial discharge detection device, insulating oil dielectric strength tester, etc With abundant of experience and professional team we have exported our products to many countries and regions all over the world, especially the Middle East area, Asian area. Eastern Europe, etc. Also our products are widely recognized and trusted by users.
The index is designed to guide the tester that all kinds of the relay protection device test can be done by the following series which modules of software.
Relay test:
Relay protection type | Test Item | Proposed test module | Remarks |
Signal relay | Corresponding test items |
DC Test
AC and DC Test |
If the intermediate relay is required AC/DC hybrid input, please test in ‘The AC And DC Test ‘module. If Rated current of the signal relay is too small, please use the voltage loop output of tester to do experiments. |
Time relay | |||
Intermediate relay | |||
Coincidence relay | |||
Other DC voltage and current relay | |||
Current relay | Corresponding test items | AC Test |
The sequence component relay can be tested in the special sequence module of ‘AC Test’. The inverse time relay can be tested in the "It characteristics" module. |
Over (under) voltage relay | |||
Sequence component relay | |||
Synchronous check (or phase comparison) relay | |||
Inverse time current relay | |||
Differential relay | DC magnetic feature |
Differential Relay, Differential Harmonic, AC/DC Test, Harmonic Test |
Please refer to ‘Appendix 5’ for correct wiring in the test |
Harmonic braking feature | |||
Proportional braking feature
|
Differential Relay, AC Test | ||
Power (directional) relay | Corresponding test items | Power Direction &Impedance, AC Test | Before testing the power (direction) relay, the type of connection and the action boundary of the protection should be determined in advance. |
Impedance relay | |||
Synchronous relay | Corresponding test items | Synchronization Test, AC Test | UA, UC of tester is fixed as the system side and the side to side voltage output for ‘Synchronization Test’ module. |
Frequency relay | Corresponding test items | High-Low Frequency Test | When the ‘automatic frequency conversion’ method is chosen in the single machine, the frequency slip value can be measured. |
Computer protection test:
Relay protection type | Test Item | Proposed test module | Remarks | |
Line protection | Multi-section over current | Corresponding test items | AC Test | As long as the method is proper, the tests of most relays and microcomputer protection can be done by the ‘AC Test’ module, which should be selective learning. |
Over (under) voltage | ||||
Sequence component voltage and current | ||||
Frequency device | ||||
Power direction protection | ||||
Reclosing and tansform fault | Corresponding test items | Full Group Test, State Series, Comprehensive Test of Line Protection of 6-35 KV Microcomputer | Requirement that if the Synchronization check and no-voltage check test is done, the Ux as the side and side voltage output and the tester is to use Ua instead of Ux for testing. | |
Distance & Zero Sequence Protection, | The Setting value verification of Distance & Zero Sequence Protection | Distance & Zero Sequence Protection, Full Group Test, AC Test | "Distance & Zero Sequence Protection” can automatically test multiple sections, various fault types and other distance and zero sequence value. | |
Characteristic of Impedance | Characteristic of Impedance | |||
Power frequency variation distance | Setting value verification | Distance & Zero Sequence Protection | The fault current should be large enough, such as 10~15A (when CT is 5A) | |
Compound voltage blocking(directional) overcurrent | Over current, low voltage, negative sequence voltage, sensitive angle | AC Test, Comprehensive Test of Line Protection of 6-35 KV Microcomputer | Some of the protection of the "low voltage" and "negative sequence voltage" input by different terminal, replacing the wiring is necessary in the test. | |
Low cycle, low voltage load shedding device | Corresponding test items | High-Low Frequency Test, Comprehensive Test of Line Protection of 6-35 KV Microcomputer | If other conditions are satisfied, the device cannot move, please confirm whether the device also need to input current and switch contacts | |
The generator transformer protection | Differential protection | Proportional braking characteristic | Differential Protection, Differential Value, AC Test |
When the differential protection is used in the differential protection of generator, it can be regarded as the transformer protection with the connection type of Y/Y, high and low voltage side balance coefficient of 1. "Differential protection" module pay attention to the curve characteristic search and the "differential value" module focuses on the differential value test. Their combination can test the differential protection. |
Harmonic braking characteristic | Differential Protection, Differential Value, Harmonic Test | |||
Loss of magnetic protection | Corresponding test items | AC Test | The angle of output voltage and current should be paid attention in the test. | |
Excitation protection | ||||
Other protection | Automatic quasi synchronization device | Corresponding test items | Synchronization Test | To do the automatic adjustment test, the line must be in accordance with the requirements of instruction when testing the input. |
Busbar differential protection | Corresponding test items | AC Test | Please see the instructions of the BP-2B and RCS-915 of "Nari part protection" on in the Appendix 6. | |
Optical fiber line differential protection | Before the test to determine whether the device to form a "self loop", if, then the protection of the action value should be equal to half of its set value. |