RS310 SF6 Gas Analyzer Automatic SF6 Gas Density Switches Meter Relay Calibrator
1.The high performance single chip microcomputer is used to detect and control the density relay, and the integration degree is high. It is mechanical and electrical integration design, high precision, good repeatability, high reliability.
2.Configuration of a monochrome LCD screen and the rotation of the switch, the operation is simple, beautiful interface, all parameters and status at a glance.
3.The pressure and temperature are automatically compensated by the automatic pressure measurement and the 20 ℃ value conversion. And display the measured ambient temperature, pressure, temperature of 20 degrees Celsius, the ambient temperature, etc. It solves the problem of SF6 gas density relay field calibration difficult thoroughly.
4.All the testing process is automatically controlled by the single chip microcomputer, without manual intervention.
Working voltage | 50Hz, AC220V |
instrument power | 55W |
Instrument precision | 0.2 |
Pressure detection range | 0 ~ 1MPa |
Pressure resolution | 0.001MPa |
Temperature display range | -20℃~80℃ |
Temperature resolution | 0.1C |
Instrument operating temperature | -10℃~60℃; |
Humidity | 90%RH |
Display mode | 320X240 graphics dot matrix monochrome LCD screen |
Mode of operation | a key shuttle (rotary mouse) |
Gas fast lock joint | all imported original device |
Printer type | high speed thermal printer |