Handheld Partial Discharge Detector High Voltage Equipment 0.85kg Weight
Product Introduction
The characteristics of RSJFS-V high frequency partial discharge detector for charged inspection, using two kinds of method to detect the high frequency current and ultrasonic wave, its small size, excellent performance, easy to operate. The cables, transformers (reactors) and ground measurement. This system uses modern electronic and computer technology, realize signal amplification (simulation. Electronic, digital), filtering, data acquisition, data processing, graphic display, automatically generated test report, thus completing the measurement of partial discharge analysis.
RSJFS-V hand held PD partial discharge tester system composition
This system mainly consists of the following parts
Technical Parameters
The Host Parameter | ||
Number of Detectable Channels | 2 | |
The Sampling Accuracy | 12bit | |
Triggered | Internal synchronization, external synchronization | |
HFCT Parameter | ||
Detection Bandwidth | 100K-50MHz | |
Transfer Impedance | >5mV/mA(10MHz ) | |
Output Impedance | 50Ω | |
Detection Sensitivity | 5pC | |
Measuring Range | -20~80dB | |
Measurement Error | ±1dB | |
Resolution Ratio | 1dB | |
Output Interface | Standard BNC | |
US Parameter | ||
Frequency Range | 20kHz-300kHz | |
Output Impedance | 50Ω | |
Detection Sensitivity | 0.1mV | |
Measuring Range | 0.1mV~1V | |
Output Interface | Standard BNC | |
Hardware | ||
Display | 4.3” TFT LCD | |
Resolution Ratio | 480×272 | |
Operation | Membrane key | |
Storage | SD card is equipped with 16g card as standard, with the maximum support of 32g | |
Power Supply | ||
Internal power supply | Battery powered (16.8v lithium battery) | |
Normal working hours | About 7 hours, full time about 5 hours | |
Size | ||
Length × width × height | 235mm×133mm×48mm | |
Weight | 0.85kg | |
Environmenta | ||
Operating ambient temperature | -20℃ to 50℃ | |
Storage ambient temperature | -40℃~70℃ | |
Humidity | 10%-90% | |
Altitude | ≤3000m |